Icons
Keys
Description
Gen Open/Close
MANual mode: Switch Generator breaker ON or
OFF
Mains Open/
Close
MANual mode: Switch Mains breaker ON or OFF
Up/Increase
1) Screen scroll
2) Setting menu: Up cursor and increase value in
Down/Decrease
1) Screen scroll
2) Setting menu: Down cursor and decrease value
Left
1) Screen scroll
2) Setting menu: Left move cursor
Right
1) Screen scroll
2) Setting menu: Right move cursor
Set/Confirm
Select viewing area
Exit
1) Returns to the main menu
2) In settings menu returns to the previous menu
Warning
Alarm
Running
Genset
Busbar
Mains
In MANual mode:
Pressing and (START) simultaneously will
force generator to crank. Successful start will not
be judged according to crank disconnect condi‐
tions, operator will have to crank the starter motor
manually; when operator decides that the engine
has fired, he/she should release the button and
start output will be deactivated, safety on delay will
start.