Manual 35018V1
505XT Digital Control System for Steam Turbines
Woodward
40
Features
Two (2) Digital Speed Sensor circuits, isolated individually
GAP configurable for MPU sensors or Proximity sensor operation
Separate terminals provided for MPU and Prox sensors
Isolated Prox Power (+24 Vdc) is provided with short-circuit protection
Woodward GAP block, diagnostics, and configuration support
GAP configurable update rates of 5 ms to 160 ms
Specifications (MPU / PROX)
MPU Input Voltage:
1 to 35 Vrms
MPU Input Frequency: 10 Hz to 35 KHz
MPU Input Impedance: 2000
Ω
, DC
MPU Input Isolation:
500 Vrms to EARTH and all other I/O
500 Vrms to other MPU and PROX channels
Prox Input Voltage:
0-32 VDC
Prox Input Frequency: 0.04 Hz to 35 KHz (low limit depends on range)
Prox Input Impedance: 2000
Ω
, DC
Prox Threshold: Low is < 8 VDC, High is > 16VDC
Prox Input Isolation:
500 Vrms to EARTH and all other I/O
500 Vrms to other MPU and PROX channels.
Prox 2 outputs:
24 VDC ± 14%, 0-200 mA, short circuit & diode protected
Prox Power Isolation: 500 Vrms to EARTH, all other I/O, & other Prox Power
Max Speed Range: software selectable from 5 kHz to 35 kHz
Accuracy (-40,70c):
< ±0.01% of full scale range selected
Resolution:
> 22 bits
Speed Filter (ms): 5-10,000 ms (2 poles)
Derivative Filter (ms): 5-10,000 ms (speed 1 pole)
Derivative Accuracy:
0.1% of full scale range, over full temperature range
Acceleration limit: 1-10,000 %/sec
Figure 2-6. Speed Sensor Block Diagram