Manual 35018V1
505XT Digital Control System for Steam Turbines
Woodward
25
Figure 1-9. Vibration Monitoring Page
If vibration probes are added to the CORE AI channels on the 505 unit instead of a LinkNet device, then
Alarm and Trip levels must be programmed in the Configurable Alarms section (up to 3 available) of the
SERVICE menu. With this option, the Vibration monitoring screens are not available.
Using External Trips on LinkNet Discrete Input Module
When External Trip signals are used on the LinkNet modules, the signal is automatically inverted. When
the signal goes FALSE, the contact is open, and then the Trip signal will be sent to the control. Unlike
External Trips wired into the CORE DI channels on the 505 unit, 1ms time stamping resolution is not
available on the LinkNet External Trip signals.
Control Communication Interfaces
Modbus
A complete Modbus list of information is available for HMI, plant DCS or other control interfaces. Three
physical ports are available for this communication method, 2 Ethernet (RJ45) ports and 1 serial port. The
serial port protocol can be either ASCII or RTU and the communications can be RS-232 or RS-485. The
Ethernet links can be configured as TCP or UDP on either ENET ports 1 or 2.
Ethernet port 3 is dedicated to use for pre-programmed communication links to other Woodward devices
(found in the Woodward Link section of the Configuration menu). The DSLC-2 and HighProtec are
examples of other products that are able to be networked to the 505XT using this port.
The control also communicates Servlink protocol (Woodward proprietary) via the Ethernet ports. Using
Woodward’s Servlink to OPC Server tool any PC can use this connection to communicate to the control
and relay OPC data to the various service tools that support the product.
CAN
The CAN communication ports are available for interfacing the control application with other products.
The 505XT has been programmed these to be used for the following:
CAN #1 Link to digital drivers/actuators (such as VariStroke family)
CAN #2 Link to LinkNet distributed I/O nodes
CAN #3 Link to Power management products (such as LS-5, MFR300)
CAN
#4
Reserved