Manual 35018V1
505XT Digital Control System for Steam Turbines
Woodward
146
CONTACT INPUT 01
FUNCTION Emergency
Stop
This channel is a dedicated trip input.
DEVICE TAG
This is a user entered field. It allows entry of a short description or tag name for this channel.
CONTACT INPUT xx
FUNCTION
(must choose from list)
Scroll through the menu by navigating the focus highlighter to the desired item, pressing ENTER,
using the Adjust Up/Down Arrows, and then pressing the ENTER key again to select the
option/function. Press the ESC key to cancel the selection.
CONTACT INPUT OPTIONS
These 3 channels are defaulted as shown – but can be modified if desired.
CONTACT INPUT 02
dflt= Reset Command
CONTACT INPUT 03
dflt= Speed Raise Command
CONTACT INPUT 04
dflt= Speed Lower Command
See tables in chapter 1 for the list of functional options:
Many of the functions in this list are described in other sections of the manual containing the functional
description. Functions that are not described elsewhere in the manual or need clarification are described
as follows:
Instant Minimum Governor – This feature will quickly ramp the speed setpoint to the configured Minimum
Governor setpoint, if configured as a mechanical drive application, or to the Minimum Load Setpoint if
configured as a generator application.
DEVICE TAG
This is a user entered field. It allows entry of a short description or tag name for this channel.
INVERT LOGIC?
dflt= NO (Yes/No)
Select this to invert this contact input. Inverting means that a function normally activated when
CLOSED or TRUE will not be activated when the contact is OPEN or FALSE. Note that this is not
required for External Trip inputs because the “Normal” or “Non-Inverted” functionality is already fail-
safe (CLOSED/TRUE = healthy, OPEN/FALSE = trip).
Contact Inputs # 3 through # 20 are entered following the same rules as described for Contact Input # 2.
Relays Menu
You may configure up to seven relays in addition to the one pre-assigned relay (Shutdown). Each relay
can be configured as either a level switch or as an indication. An example of a level switch is a Speed
Switch and an example of an indication is Cascade Control Enabled.
RELAY OUTPUT 01
RELAY OUTPUT FUNCTION
Trip Relay
This channel is a dedicated trip output.
DEVICE TAG
This is a user entered field. It allows entry of a short description or tag name for this channel.
RELAY OUTPUT 02
USE AS LEVEL SWITCH?
dflt= NO (Yes/No)
Select this to use this relay output as a level switch. Otherwise, the relay output will be a status
indication.
RELAY OUTPUT FUNCTION
(must choose from list)
Scroll through the menu by navigating the focus highlighter to the desired item, pressing ENTER,
using the Adjust Up/Down Arrows, and then pressing the ENTER key again to select the
option/function. Press the ESC key to cancel the selection.