Table 6-14. Analog Read register (3:0236) Map Limiter Status Messages
Value
Description
Value
Description
0
No Map Limits
16
Map Limit - Min Flow & Min P -
1
LP Limiter -
17
Map Limit - Min Flow & Min LP -
2
Map Limit - Min LP & Max HP -
18
Map Limit - Max P -
3
Map Limit - Min LP & Min P -
19
Map Limit - Min P -
4
Map Limit - Min LP & Min HP -
20
Map Limit - Max S -
5
Map Limit - Min LP & Max P -
21
Map Limit - Max LP -
6
Map Limit - Max P & Max HP -
22
Map Limit - Min LP -
7
Map Limit - Max P & Max S -
23
Map Limit - Max HP -
8
Map Limit - Max P & Max LP -
24
Map Limit - Min HP -
9
Map Limit - Max HP & Max S -
25
Map Limit - Min Flow -
10
Map Limit - Max HP & Max LP -
11
Map Limit - Max LP & Max S -
12
Map Limit - Max LP & Min P -
13
Map Limit - Max LP & Min HP -
14
Map Limit - Min HP & Min P -
15
Map Limit - Min P & Max S -
Table 6-15. Analog Read register (3:0001) Control Status
Value
Description
Value
Description
23
Shutdown
14
Ready to Start
22
Controlled Shutdown
13
Manual Start
24
Transferring to Ratio Limiter Control
12
Auto Start
25
Transferring to Speed Only Controll
11
Semi Auto Start
26
LP Limiter Ramping
10
Idle / Rated Start
20
Max Actuator
9
Auto Start Sequence
27
HP Valve Limiter and LP Valve
Limiter 8
Synchronizing
19
HP Valve Limiter
7
Load Share / Speed
28
Acceleration Limiter
6
Frequency / Speed
29
Manual Demand
34
Full Decoupled - Speed/Extraction
18
Remote Auxiliary
35
Ratio Limiter Control
17 Auxiliary
Control
5 Remote
Cascade/Speed
30 Remote
Inlet
4
Cascade / Speed
31
Inlet in Control
3
Remote Speed
32 Remote
Exhaust
36
Remote / KW
33
Exhaust in Control
2
Speed / On-Line
16 Configuration Error
1
Speed / Off-Line
15
Start Perm Not Met
Analog Read addresses 3:0088—0093 and 3:0148—0149 give the configuration value of the analog
inputs in order. The configuration for the analog inputs are defined in the table below.
Содержание 505XT
Страница 33: ...Manual 35018V1 505XT Digital Control System for Steam Turbines Woodward 31 Figure 2 2 505D Outline Drawing ...
Страница 240: ...Manual 35018V1 505XT Digital Control System for Steam Turbines Woodward 238 Declarations ...
Страница 241: ...Manual 35018V1 505XT Digital Control System for Steam Turbines Woodward 239 ...