Manual 35018V1
505XT Digital Control System for Steam Turbines
Woodward
150
Configuration Error Messages
The control automatically performs a check on the configured values to assure that required program
blocks have values loaded into them. This check cannot determine if the values entered are realistic but it
makes sure that values have been loaded into required parameters. If any errors are found in the
program, the 505XT will remain in a shutdown state and a banner message will appear on the
Configuration Menu and MODE screens. They can be displayed by pressing the ‘Config Check’ softkey
on the Configuration Menu screen.
The configuration error message alerts you that a configuration change is required before the 505 can
operate the turbine. All errors must be corrected before in order to be able to reset the 505 to the “Ready
to Start” condition.
The figure below identifies the various configuration error messages that may appear and explains the
meaning of the error.
Table 4-3. Configuration Error Messages
Event
ID
Description Error
Meaning
1 Duplicate
Contact
Input
Channel
Two contact inputs were programmed for the same function.
2
Contact Input Error
Should never appear (always FALSE) since Contact Input 01 is
hard coded as a trip input.
3
Contact Input 02 Error
The specified contact input was configured for a function that is
not configured as used. Either the contact input was mis-
configured or the function required is mis-configured. For example,
contact input #1 is programmed for Remote Cascade Set Point
Enable but Remote Cascade Set Point was not programmed
under the Cascade configure menu.
4
Contact Input 03 Error
See "Contact Input 02 Error".
5
Contact Input 04 Error
See "Contact Input 02 Error".
6
Contact Input 05 Error
See "Contact Input 02 Error".
7
Contact Input 06 Error
See "Contact Input 02 Error".
8
Contact Input 07 Error
See "Contact Input 02 Error".
9
Contact Input 08 Error
See "Contact Input 02 Error".
10
Contact Input 09 Error
See "Contact Input 02 Error".
11
Contact Input 10 Error
See "Contact Input 02 Error".
12
Contact Input 11 Error
See "Contact Input 02 Error".
13
Contact Input 12 Error
See "Contact Input 02 Error".
14
Contact Input 13 Error
See "Contact Input 02 Error".
15
Contact Input 14 Error
See "Contact Input 02 Error".
16
Contact Input 15 Error
See "Contact Input 02 Error".
17
Contact Input 16 Error
See "Contact Input 02 Error".
18
Contact Input 17 Error
See "Contact Input 02 Error".
19
Contact Input 18 Error
See "Contact Input 02 Error".
20
Contact Input 19 Error
See "Contact Input 02 Error".
21
Contact Input 20 Error
See "Contact Input 02 Error".
22
Duplicate Analog Input
Channel
Two analog inputs were programmed for the same function.