Manual 35018V1
505XT Digital Control System for Steam Turbines
Woodward
155
Event
ID
Description Error
Meaning
99
Maximum Speed >
Probe 1 Freq Range
The maximum speed input is 35000 hertz. This is a limitation of
the 505’s hardware/speed sensing circuitry. The frequency input of
the speed sensor must be less than this value. The gear the
speed sensor is mounted on may need to be changed to one with
less teeth, this will decrease the frequency seen by the speed
probes. The Maximum Speed Level for Speed Input Channel 1,
converted to frequency (Hz), is greater than 35000 Hz.
100
Maximum Speed >
Probe 2 Freq Range
The maximum speed input is 35000 hertz. This is a limitation of
the 505’s hardware/speed sensing circuitry. The frequency input of
the speed sensor must be less than this value. The gear the
speed sensor is mounted on may need to be changed to one with
less teeth, this will decrease the frequency seen by the speed
probes. The Maximum Speed Level for Speed Input Channel 2,
converted to frequency (Hz), is greater than 35000 Hz.
101
Speed Sensor #1 Failed
< Freq Range
The failed speed setting for speed input #1 is below the minimum
allowed setting. The minimum allowed setting is calculated as
follows: (Maximum Speed Level) * (0.0204).
102
Speed Sensor #2 Failed
< Freq Range
The failed speed setting for speed input #2 is below the minimum
allowed setting. The minimum allowed setting is calculated as
follows: (Maximum Speed Level) * (0.0204).
103
No Start Mode
Configured
No start mode is selected in the Configure mode. One of the three
start modes must be selected in the Configure mode under the
Start menu.
104
Remote KW Setpoint
Configured, No AI
The Remote kW Setpoint is configured as used but no analog
input is configured as a Remote kW Setpoint.
105
Remote Speed and KW
Setpoint
Both Remote Speed Setpoint and Remote kW Setpoints are
configured as used. Only one of these inputs may be configured.
106
Hot Start greater than
Cold Start
The time configured for a Hot Start is greater than the Cold Start.
The time remaining after shutdown for a Hot Start must be less
than the time for a Cold Start.
107
Hot Reset Timer Level
Error
Hot Reset Timer Level is greater than the Maximum Governor
speed level or less than the Minimum Governor speed level. The
Hot Reset Timer Level must be between Minimum and Maximum
Governor.
108
Temperature 1 or 2
used, no AI
A Start Temperature function is configured but no Analog Input is
configured as a temperature input.
109
Cascade Speed Limit
Error
The Cascade minimum speed limit is configured less than
Minimum Governor, the Cascade maximum speed limit is
configured greater than Maximum Governor, or the Cascade
minimum speed limit is greater than the Cascade maximum speed
limit.
110
KW Signal Source Not
Selected
A controller has been configured to use a kW input but no Primary
or Secondary Signal source has been selected under Operating
Parameters.
111
SYNC Signal Source Not
Selected
A controller has been configured to use a Synchronization input
but no Primary or Secondary Signal source has been selected
under Operating Parameters.