Manual 35018V1
505XT Digital Control System for Steam Turbines
Woodward
154
Event
ID
Description Error
Meaning
81
Idle 2 Setpoint >
Minimum Governor
The Idle Speed setpoint is configured at a higher speed than the
minimum governor speed setpoint.
82
Idle 3 Setpoint >
Minimum Governor
The Idle Speed setpoint is configured at a higher speed than the
minimum governor speed setpoint.
83
Idle 1 > Idle 2
The Idle 1 speed setpoint is configured at a higher speed than the
Idle 2 speed setpoint.
84
Idle 2 > Idle 3
The Idle 2 speed setpoint is configured at a higher speed than the
Idle 3 speed setpoint.
85
Rate to Idle 2 Error
The Cold Rate to Idle 2 (rpm/second) is configured at a higher rate
than the Hot Rate to Idle 2. Or the Warm Rate to Idle 2 (if used) is
configured at a higher rate than the Hot Rate to Idle 2.
86
Rate to Idle 3 Error
The Cold Rate to Idle 3 (rpm/second) is configured at a higher rate
than the Hot Rate to Idle 3. Or the Warm Rate to Idle 3 (if used) is
configured at a higher rate than the Hot Rate to Idle 3.
87
Rate to Rated Error
The Cold Rate to Rated (rpm/second) is configured at a higher
rate than the Hot Rate to Rated. Or the Warm Rate to Rated (if
used) is configured at a higher rate than the Hot Rate to Rated.
88
Critical Band Rate <
Slow Rate
The acceleration rate (rpm/second) through the critical speed
avoidance band must be faster than the normal speed set point
rate.
89
Critical Speeds Enabled,
No Idle
A critical speed avoidance band is configured but neither idle/rated
nor auto start sequence is configured. To use the critical speed
avoidance logic one of these functions that uses an idle speed
must be programmed.
90
Critical Band Below 1st
Idle Setpoint
A critical speed avoidance band is configured below either the Idle
speed set point (when using Idle/Rated) or the Idle 1 set point
(when using the Automatic Start sequence).
91
Critical Band > Minimum
Governor
A critical speed avoidance band is configured higher than the
Minimum Governor speed level.
92
Critical Band Min > Max
A critical speed avoidance band minimum limit is configured
higher than the maximum limit of that band.
93
Minimum Governor >
Maximum Governor
The Minimum Governor speed level is configured higher than the
Maximum Governor speed level.
94
Rated Speed < Min Gov
The Rated speed set point is configured at a lower speed than the
Minimum Governor speed set point.
95
Rated Speed > Max Gov The Rated speed set point is configured at a higher speed than
the Maximum Governor speed set point.
96
Max Gov > Overspeed
Test Limit
The Maximum Governor speed level is configured greater than the
Overspeed Test Limit.
97
Overspeed Trip >
Overspeed Test SP
The Overspeed Trip setpoint is greater than the Overspeed Test
Limit.
98
Overspeed Test Limit >
Maximum Speed
The Overspeed Test Limit is configured greater than the Maximum
Speed Level for speed input 1 or 2 (if used).