Manual 35018V1
505XT Digital Control System for Steam Turbines
Woodward
181
Event
ID DESCRIPTION
MEANING
125
Alternate Mode Map Error
Steam Map values entered will cause potentially unstable control in
an Alternate Mode. Verify correct sign on resulting D values
126
LP Valve Pos Fdbk Diff ALM
LP Demand versus Feedback Difference
127
LP Linearization Alarm
Output valve curve error on X-Y points
128
spare_128
reserved - not used
129
spare_129
reserved - not used
130
spare_130
reserved - not used
Shutdown Summary
The Shutdown Summary screen is always available with the VIEW button under the TRIPPED LED.
When a trip is detected, it gets latched in the event logic, the Trip relay is de-energized, all steam valve
demand outputs go to zero, and the TRIPPED LED illuminates (Red). The cause of the event will be
indicated with an Event ID, description and time/date stamp on the Shutdown Summary page. The list will
always place the first event at the top of the list, if more than one trip condition is present they will all be
listed with their corresponding time stamp.
To clear any shutdowns that are no longer present, press the RESET key, close the Reset contact input,
or select Reset from either Modbus communications link. If the cause of the event has been corrected the
event will clear, it not it will remain and the time-stamp will remain unchanged.
Figure 5-31. Shutdown Summary Screen
The table below lists all the potential shutdown conditions.
Table 5-2. TRIPPED Messages
Event
ID DESCRIPTION
MEANING
1 External Trip Input 1
External Trip contact input was opened
2 Emergency Stop Button
Front Panel Display Emergency Stop was pressed
3 Overspeed
Turbine overspeed was sensed
4 All Speed Probes Failed
Loss of all speed probes was sensed
5 HP Actuator Fault
HP Actuator fault detected (an open or short circuit was
sensed)
6 HP2 Actuator Fault
HP2 Actuator fault detected (an open or short circuit was
sensed)