Manual 35018V1
505XT Digital Control System for Steam Turbines
Woodward
27
VIEW buttons will jump to the Trip or Alarm Summary screen to show these events in sequence with time
stamp.
MODE button will jump to a Login screen that allows the user to view current permissions and allow
access to changing the user login level
ESC Key – this will always step the user ‘back’ one page from the current page displayed
HOME Key
Brings the user to the Home menu for Run, Service, or Configure. Pressing it a second time will return to
the Run (Operate) Menu Home Screen
NAVIGATION CROSS KEYS
These are the primary keys for navigating from page to page, or for navigation of the FOCUS on any
page.
Soft Key Commands – Dependent on the screen currently in view – the user must use the navigation
cross keys to move the “Focus” to the desired component
GREEN KEYS
Generally perform Operational Actions – such as Enabling, Disabling, Starting, Stopping, Tuning or
Adjusting values
MAROON KEYS
Generally perform Navigational actions that escort the user through the screen menus
BLACK KEYS
Are soft-key functions that relate to the display indication above them. They can be navigational or
operational. These items do not require “Focus”, they are always available on that particular screen.
Screen
Tutorial
The 505 has a detailed Tutorial that is always accessible through the
Service Menu. It provides ‘On-Screen’ help on topics such as
Navigation, User Levels, Operating Modes, how to adjust parameters,
and more. The User should familiarize themselves with these screens
Watchdog Timer/CPU Fault Control
The IO Lock and CPU Health LED’s on the front left side of the display – are always in an identical state
as the LED’s on the back side of the control. They are completely controlled by the 505 control hardware
and are not controlled by the GAP application.
A watchdog timer and CPU fault circuit monitors the operation of the microprocessor and microprocessor
memory. If the microprocessor fails to reset the timer within 15 milliseconds of the last reset, the CPU
fault-control will activate the reset output. This resets the CPU, de-energizes all relay outputs and turns
off all milliamp outputs.