Manual 35018V1
505XT Digital Control System for Steam Turbines
Woodward
230
Remote Inlet Max Rate
5
Units/s
Inlet Units of Measure
User text
Decimals Displayed
1
value
EXHAUST PRESSURE
CONTROL
Default
Site
Value
Use Exhaust Pressure Control ?
NO
YES/NO
Lost Exhaust Input Shutdown?
NO
YES/NO
Invert Exhaust ?
NO
YES/NO
Min Exhaust Setpt
0
Units
Max Exhaust Setpt
100
Units
Exhaust Setpt Rate units/s
5
Units/s
Use Exhaust as a Controller?
NO
YES/NO
Setpt Initial Value
0
Units
Use Droop?
NO
YES/NO
Exhaust Droop
0
%
Exhaust PID Prop Gain
1.00
%
Exhaust PID Integral Gain
0.300
rps
Exhaust Derivative Ratio
100
%
Use Remote Exhaust Setpoint
NO
YES/NO
Remote Exhaust Max Rate
5
Units/s
Exhaust Units of Measure
User text
Decimals Displayed
1
value
EXTR / ADM CONTROL
Default
Site
Value
Use Extraction /Admission Control ?
NO
YES/NO
Lost E/A Input = Trip ?
NO
YES/NO
Min Extr/Adm Setpt Units
0
Units
Max Extr/Adm Setpt Units
100
Units
Setpoint Rate (units/sec) Units
5
Units/s
Use Setpoint Tracking?
NO
YES/NO
Setpoint Initial Value Units
0
Units
Use Droop?
NO
YES/NO
Extr/Adm Droop %
0
%
PID Proportional Gain %
1
%
PID Integral Gain rps
0.30
rps
PID Derivative Ratio %
100
%
Tiebrkr Open E/A Disable
YES
YES/NO
Genbrkr Open E/A Disable
YES
YES/NO
Generator Breaker Open Extr/Adm Inhibit?
YES
YES/NO
Use Remote Setting?
NO
YES/NO
Remote Setpt Max Rate Units
5
Units/s
Ext/Adm Units Of Measure
Units
Decimals Displayed
1
Allow use of Full Decoupled Mode?
NO
YES/NO