Design information
The safety valve is in
-
tegrated into the boiler
Design example - Injection control
Abb.
Product
GT
Boiler type CGB-35/50
RK
Check valve - opening pressure 20 mbar
HKAS
Heating circuit connection set
comprising:
2 ball valves 1"
2 fill & drain valves
SMF
Dirt trap 1¼“
DV 1,2
Reducer
KH
Ball valve 1"
BS
Dummy plug - same internal diameter as the mixer
MI
Three-way mixer
DN 20 k
VS
6,3
up to 45 kW with injection control
(heating curve distance 10 K)
DN 25 k
VS
12
> 45 kW with injection control
(heating curve distance 10 K)
Mixer motor
VF
Flow sensor (part of the standard delivery of the
MM
R
control unit - weather-compensated thermostat incl. flow sensor
V
Pipework
Pipework in the mixer circuit (MK)
Flow, return, bypass in the mixer circuit
Flow volume MK
∆T
Rated output
Internal diameter - pipework
VMI
bis 1290 l/h
10 K
bis 20 kW
DN 25
bis 2000 l/h
10 K
bis 30 kW
DN 32
bis 3440 l/h
10 K
bis 45 kW
DN 40
bis 5160 l/h
10 K
bis 60 kW
DN 50