Condensate connection
Connect the supplied sealed siphon to the connector on
the condensate sump.
Note: Fill the siphon with water, prior to commissio-
ning
The condensate may be routed into the siphon below
the safety valve, if neutralisation is not required.
If condensate is directly routed to the public sewer, en
-
sure ventilation, so that the public sewer cannot affect
the condensing boiler.
Fig.: Siphon
Siphon
Tab
Fig.: Push in the tab
Observe the relevant instructions if you install a neutra
-
lising system (accessory).
Fig.: Neutralising system (accessory)
Installation
Connection of a 200 litre Wolf DHW cylin
-
der or third party cylinder
Connect the DHW flow and return with a three-way
diverter valve or the return pipe of the gas fired boiler.
Use a DHW sensor from the Wolf accessory range when
connecting a DHW cylinder made by third parties. A
detailed description is included with the connection set
(accessories).
Check all water connections for possible
leaks, prior to commissioning:
Test pressure (DHW side): max. 10 bar
Test pressure (heating water side): max.
4.5 bar.
If the system leaks, water may seep out,
resulting in material losses.