28
3061490_0709
Displaying/modifying control parameters
Modifications must only the carried out by
a recognised heating contractor or by Wolf
customer service.
Incorrect operation can lead to system
faults.
Please note when using parameter
GB 05 (frost protection/outside tempera
-
ture), that frost protection is not safeguar
-
ded if you set temperatures lower than 0 °C.
This can lead to heating system damage.
For output details of this boiler, see the
type plate.
To prevent damage to the heating system,
cancel night setback when outside tempe
-
ratures fall below -12 ° C. If this rule is not
observed, ice may form on the flue outlet
which may result in injury to individuals or
material losses.
NB
NB
1
2
Parameter
Unit
Factory setting
min
max
GB01
HG01
Flow temperature hysteresis
K
8
5
30
HG02
Lower fan speed
Min. fan speed in %
%
CGB-35: 31
CGB-50: 29
31
29
100
100
HG03
Upper fan speed DHW
Max. fan speed in % for DHW
%
CGB-35: 100
CGB-50: 100
31
100
GB04
HG04
Upper fan speed central heating
Maximum fan speed in % for central heating
%
CGB-35: 100
CGB-50: 100
31
100
GB05
A09
Frost protection outside temperature
With connected outside temperature sensor and
insufficient temperature pump ON
°C
2
-10
10
GB06
HG06
Heating circuit pump mode
0 → Pump ON in winter mode
1 → Pump ON when the burner is ON
0
0
1
GB07
HG07
Heating circuit pump run-on time
Heating circuit pump run-on time in heating mode in min.
Heating circuit pump run-on time in heating mode in min.
min
1
0
30
GB08
HG08 or
HG22
Maximum set flow temperature
Applies to heating mode
°C
80
40
90
GB09
HG09
Cycle block
applies to heating mode
min
7
1
30
HG10
e Bus address
Bus address of boiler (display only)
0
0
5
HG11
DHW quick start-up
Temperature of plate heat exchanger in summer mode
(suitable for combi-boilers only)
°C
10
10
60
HG12
Gas type
not assisted
0
0
1
GB13
HG13
Input E1
Input E1 (24 V)
Various functions can be allocated to input E1.
See chapter „Connection input E1“
1
Roomthermostat
0
5
GB14
HG14
Output A1 (230VAC)
Various functions can be allocated to output A1.
See chapter „Connection output A1“
6
Cylinder primary
pump
0
9
GB15
HG15
DHW cylinder hysteresis
Switching differential for cylinder reheating
5
1
30
HG21
Minimum boiler water temperature TK-min
°C
20
20
90
The control parameter can be modified or displayed via controller with eBUS capability. For procedures, check the
operating instructions of the relevant accessories.
Settings of column 1 are suitable for control accessories ART and AWT.
Settings of column 2 are suitable for Wolf control systems with BM (programming unit)
Содержание CGB-35