Design information
1)
Available fan draught: CGB-35 115 Pa, CGB-50 145 Pa
2)
For calculating the pipe length, see section "Calculating the balanced flue pipe length", page 42.
Note: Systems C 33x and C 83x are also suitable for installation in garages.
Where necessary, adapt the installation examples to the relevant Building Regulations and requirements of your
country/region. Discuss any questions relating to the installation, in particular regarding the installation of inspection
parts and ventilation apertures, with your local heating engineer.
For concentric air/flue pipes (balanced flue systems), only use original Wolf components.
Flue gas/ventilation air routing options system
Condensing boiler versions
Max. length
1) 2)
[m]
CGB-35
CGB-50
B23
Flue pipe inside a duct and combustion air
directly via the boiler (open flue)
DN 80
DN 100
30
35
20
28
B33
Flue pipe inside a duct with horizontal
concentric connection pipe (open flue)
DN 80
DN 100
30
35
20
28
B33
Resistant flue gas chimney
with vertical concentric connection pipe
(open flue)
Calculation acc. to
DIN EN 13384
(LAS manufacturer)
C13x
Horizontal concentric roof outlet through a pitched roof,
(balanced flue - on-site dormer)
20
11
C33x
Vertical concentric roof outlet through a pitched roof
or flat roof, vertical concentric balanced flue routing
for installation in a duct, (balanced flue)
22
13
C33x
C93x
Vertical flue pipe for routing through a ducts
rigid/flexible with horizontal concentric connection pipe
DN 80
DN 100
22
30
15
22
C43x
Connection to a moisture-resistant balanced flue chimney
(LAS) maximum pipe length from the centre of the boiler bend
to the connection 2 m (balanced flue)
Calculation acc. to
DIN EN 13384
(LAS manufacturer)
C53
Connection to the flue pipe inside a duct and
air supply pipe through an outside wall (balanced flue)
DN 80
DN 100
30
35
20
28
C53x
Connection to a flue pipe on an outside wall
(balanced flue)
DN 80
22
15
C83x
Connection to the flue pipe inside a duct and
air supply through an outside wall (balanced flue)
DN 80
DN 100
30
35
20
28
C83x
Concentric connection to a moisture-resistant
flue gas chimney and combustion air through
outside wall (balanced flue)
Calculation acc. to
DIN EN 13384
(LAS manufacturer)