Installation and operating instructions • Drive for Wilo-Helix2.0-VE / Wilo-Medana CH3-LE • Ed.01/2022-06
(*) The configuration of the key lock makes it possible to protect the pump setting from
being changed on the display.
9.3
Pump operation
9.3.1
Adjusting the pump output
The system was designed for a certain duty point (full load point, calculated maximum
heating or cooling power demand). During commissioning, the pump output (delivery head)
is set according to the duty point of the system. The factory setting does not correspond to
the output required for the system. The required pump capacity is determined with the help
of the pump curve diagram for the selected pump type (e.g. from the data sheet).
NOTICE
For water applications, the flow rate value shown in the display or output
to the building management system applies. For other fluids, this value
only reflects the tendency. If no pressure sensor is installed, the pump
cannot indicate a volume flow value.
9.3.2
Setting on pump
Carry out settings by turning and pressing the operating button. Turn the operating button
to the left or right to browse the menus or configure settings. A green focus indicates nav-
igation in the menu. A yellow focus indicates a configuration of settings.
Control settings
Control mode
Setpoint Δp-v
Emergency operation
Fig. 19: Green focus: Navigation in menu
•
Green focus: Navigation in menu
•
Yellow focus: Change settings
•
Turn
: Menu selection and parameter setting.
•
Press
: Activation of menus or confirming settings.
•
Press the Back button (table "Description of operating elements") to change the focus
back to the previous focus. Consequently, the focus moves one level further up in the
structure or to a previous setting.
•
Pressing the Back button after having changed a setting (yellow focus) without con-
firming the changed value returns the focus to the previous focus. The adjusted value will
be discarded. The previous value remains unchanged.
•
If the back button is pressed for more than 2 seconds, the Home screen opens and the
pump can be operated from the main menu.
Control mode
Δp-v
Δp-c
n-c
Fig. 20: Yellow focus: Change settings
NOTICE
The modified settings are stored in memory after a 10s delay. If a power
supply interruption occurs within this time, these settings will be lost.
NOTICE
If there are no warning or error messages, the display on the electronic
module will switch off 2 minutes after the last time it was operated.
- If the operating button is pressed or turned again within 7 minutes, the
previously exited menu will appear. You can continue to configure set-
tings.
- If the operating button is not pressed or turned for more than 7 minutes,
any unconfirmed settings will be lost. Pressing the button again opens the
home screen on the display and the pump can be operated from the main
menu.