en
Installation and operating instructions • Drive for Wilo-Helix2.0-VE / Wilo-Medana CH3-LE • Ed.01/2022-06
61
Set control mode
Function Anlogue input
AI 1
Function Anlogue input
AI 2
Dp-c
Configured as actual value input:
•
Type of use: differential pressure sensor
Configurable:
•
Signal type
•
Sensor measuring range
Not Configured.
Can be used as setpoint input
n-c
Not used
Not Configured.
Can be used as setpoint input or pressure
sensor input (suction pressure)
PID
Configured as actual value input:
•
Type of use: freely
Configurable:
•
Signal type
Not Configured.
Can be used as setpoint input or pressure
sensor input (suction pressure)
p-c
Configured as actual value input:
•
Type of use: pressure sensor
Configurable:
•
Signal type
Sensor measuring range
Not Configured.
Can be used as setpoint input or pressure
sensor input (suction pressure)
The analog input AI 1 is used mainly as pressure value input. The analog input AI 2 is used
mainly as the setpoint input, but with control modes n-c, PID and p-c it can be used as
sensor input for pressure sensor at suction port to support optional function “Lack of water
detection via pressure sensor”. In this case, the pressure sensor must be configured as AI 2
accordingly.
Overview of the terms for external interfaces and menu items for analog inputs AI1 and AI2
in the available languages:
External interfaces
Analog input (AI1)
Analog input (AI2)
Wilo Net settings
Universal
Display text
1.3
External interfaces
1.3.3
Analog input (AI1)
1.3.3.1
Signal type (AI1)
1.3.3.2
Pressure sensor range (AI1)
1.3.4
Analog input (AI2)
1.3.4.1
Signal type (AI2)
1.3.4.2
Pressure sensor range (AI2)
1.3.4.3
Pressure sensor type (AI2)
1.3.4.1 /1
Absolute pressure sensor
1.3.4.2 /2
Relative pressure sensor
NOTICE
The 24 V DC power supply is only available if the analog input AI 1 or AI 2
has been configured for a type of use and a signal type or if the digital in-
put DI 1 has been configured.
13.4.1
Use of analogue input AI 1 as
sensor input (actual value)
The actual value sensor provides:
•
Differential pressure sensor values for:
Differential pressure control
•
Relative pressure sensor value for:
Constant pressure control
•
User-defined sensor values for:
PID control
Содержание Helix2.0-VE
Страница 2: ......
Страница 3: ...3 English 4...
Страница 89: ......
Страница 90: ......
Страница 91: ......