en
Installation and operating instructions • Drive for Wilo-Helix2.0-VE / Wilo-Medana CH3-LE • Ed.01/2022-06
27
Fig. 16: Electronic module
The graphic display can be turned in 90° steps. To do this, open the upper part of the elec-
tronic module using a screwdriver.
The graphic display is fixed in position by two snap-in hooks.
1.
Carefully open the snap-in hooks with a tool (e.g. screwdriver).
2.
Turn the graphic display to the desired position.
3.
Fix the graphic display with the snap-in hooks.
4.
Fit the upper part of the module again. Observe the screw tightening torques on the
electronic module.
Component
Fig./item Screw
(nut)
thread
Tightening torque
Nm ± 10 % (unless
otherwise stated)
Information
Installation
Electronic module upper part
Fig. 16, pos. 1
Fig. 1, pos. 2
M5
4.5
Threaded cable gland union nut
Fig. 8, pos. 1
M25
11
*
Threaded cable gland
Fig. 8, pos. 1
M25x1.5
8
*
Threaded cable gland union nut
Fig. 8, pos. 6
M20x1.5
6
*
Threaded cable gland
Fig. 8, pos. 6
M20x1.5
5
Power terminal and control terminal Fig. 9
Pusher
Slot 0.6x3.5
**
Earthing screw
Fig. 9, pos. 5
M5
4.5
CIF module
PT 30x10
0.9
Cover Wilo-Connectivity interface
Fig. 16
M3x10
1.3
Table 7: Tightening torques for electronic module
* Tighten when installing the cables.
** Press with screwdriver to plug and unplug the cable.
8
Installation of CIF module
DANGER
Risk of fatal electrical shock!
Immediate risk of fatal injury if live components are touched!
Check whether all connections are voltage-free!
CIF modules (accessories) are used for communication between pumps and building man-
agement systems. CIF modules are plugged into the electronic module (Fig. 16, item 4)