Installation and operating instructions • Drive for Wilo-Helix2.0-VE / Wilo-Medana CH3-LE • Ed.01/2022-06
71
Ramp times
Ramp times:
Start-up time
Ramp times:
Switch-off period
Universal
Display text
1.6
Additional settings
1.6.2
Ramp times
1.6.2.1
Ramp times: start-up time
1.6.2.2
Ramp times: shut-down time
1.
"Additional settings"
2.
"Pump ramp times"
The ramp times define how fast the pump may start up and shut down at the maximum when
the setpoint is changed.
15.3
PWM frequency reduction
In the "Settings" menu
Universal
Display text
1.6
Additional settings
1.6.4
Automatic PWM frequency reduction
1.
"Additional settings"
2.
"Automatic PWM frequency reduction"
The "Automatic PWM frequency reduction" function is switched off at the factory. If the
ambient temperature is too high, the pump will automatically reduce its hydraulic power
due to the too high temperature inside the drive. If this reduced hydraulic power leads to a
too low pump output for the application, it is possible to automatically reduce the PWM
frequency of the drive by switching it ON via this menu.
As a result, the pump automatically switches to a lower PWM frequency when a critical,
defined temperature in the drive is reached. By doing so, the required pump output is
achieved.
NOTICE
Due to the automatic PWM frequency reduction, the operating noise of
the pump can increase or change.
16
Diagnostics and measured val-
ues
In order to support fault analysis, the pump provides additional help apart from fault noti-
fications:
The Diagnostics help and the measured values are used for diagnosis and maintenance of
electronics and interfaces. Apart from hydraulic and electrical overviews, information about
interfaces and device information are provided.
Overview of the terms in the display for selecting the diagnostics and measured values in
the available languages:
Diagnostics and
measured values
Diagnostics help
Measured values
Universal
Display text
2
Diagnosis and measured values
2.1
Diagnostics help
2.1.3
Overview of relay output (SSM/SBM)
2.1.4
Overview of analog input (AI1)
2.1.5
Overview of analog input (AI2)
2.1.1
Device information
2.1.2
Service information
2.1.6
Double pump connection info
2.1.7
Pump cycling status
2.2
Measured values
2.2.1
Operating data
2.2.2
Statistics data
16.1
Diagnostic help
In the menu “Diagnostics and measured values” there are:
1.
"Diagnostics help"