Installation and operating instructions • Drive for Wilo-Helix2.0-VE / Wilo-Medana CH3-LE • Ed.01/2022-06
67
Wilo Net settings
Wilo Net termination
Wilo Net address
Universal
Display text
1.3
External interfaces
1.3.5
Wilo Net settings
1.3.5.1
Wilo Net termination
1.3.5.2
Wilo Net address
1.
“External interfaces”
2.
"Wilo Net setting"
3.
"Wilo Net termination"
Possible selection:
Wilo Net termination
Switched OFF
Switched ON
Wilo Net termination
Description
Switched on
Terminating resistor of the pump is switched on. If the
pump is connected at the end of the electrical bus
line, “Switched on” must be selected.
Switched off
The pump’s terminating resistor is switched off. If the
pump is NOT connected at the end of electrical bus
line, “Switched off” must be selected.
After termination is done, an individual Wilo Net address is assigned to the pumps:
In the "Settings" menu , select:
Universal
Display text
1.3
External interfaces
1.3.5
Wilo Net settings
1.3.5.1
Wilo Net termination
1.3.5.2
Wilo Net address
Wilo Net address
1.
“External interfaces”
2.
"Wilo Net setting"
3.
"Wilo Net address” and assign an address (1 ... 21).
NOTICE
The settings range for the Wilo Net address is 1 ... 126, all values in the
range 22 … 126 must not be used.
Example double pump:
•
Pump installed at left side (l)
Wilo Net termination: ON
Wilo Net address: 1
•
Pump installes on right side (II)
Wilo Net termination: ON
Wilo Net address: 2
14
Display settings
Universal
Display text
1.5
Display settings
1.5.1
Display brightness
1.5.2
Language
1.5.3
Unit
1.5.4
Key lock
1.5.4.1
Key lock ON
General settings are made under ”Settings”, “Display settings”.