English
Installation and operating instructions Wilo-DrainLift M2/8
27
• The placement of any existing or still-to-be installed inlet, pressure and vent lines is to be
checked with regard to connection options to the unit.
• Observe the installation and operating instructions for the accessories!
7.2 Installation
Place the unit on a flat solid floor and align.
In accordance with EN{12056-4, sewage lifting units must be installed so that they cannot
twist and turn.
Units which threaten to float must be installed so that they are anti-buoyant.
7.3 Connecting the pipes
All pipes must be installed so that they are stress-free, noise-insulated and flexible. No
pipeline forces or torques may act on the unit. The pipes (incl. valves) are to be fastened
and supported such that neither tensile nor compressive forces act on the unit.
All line connections must be made with care. Carefully tighten any connections with hose
clips
(starting torque 5 Nm!).
Do not reduce the pipe diameter in the direction of flow.
In the inlet pipe in front of the tank as well as after the non-return valve, a gate valve is
always necessary in accordance with EN{12056-4. (Fig. 11).
7.3.1 Pressure pipeline
CAUTION! Risk of damage!
Occurring pressure surges (e.g. when closing the non-return valve) can sometimes be
several times more than the pump pressure, depending on the operating conditions
(to avoid this, see also sect. 8.2.2 “Setting the pump run time
”
).
• Therefore, in addition to the corresponding pressure resistance, also pay attention to
the longitudinal force fit connection elements of the pipe!
• The pressure pipeline with all installed parts must reliably withstand the occurring ope-
rating pressures.
To protect against any backflow out of the main public sewer, the pressure pipeline is to
be designed as a “pipe loop”, the bottom edge of which must lie at the highest point above
the locally defined backflow level (usually at street level). (see also Fig. 11).
The pressure pipeline is to be installed so that it is frost-proof.
Mount the gate valve (DN 80) to the pressure connection of the unit (available as an acces-
sory, nuts, washers, flat gasket included). Support the weight of the valves!
Fig. 3: Attachment of the sound absorption strips
For the sound-insulating installation of the unit, stick the
enclosed sound absorption strips in the recesses in the tank
floor provided for this purpose (see Fig. 3, item{1).
1
Fig. 4: Buoyancy safeguard
Fix the unit to the floor with the enclosed fixation material
(Fig. 4).
• Mark the position of the drilled holes on the floor for fas-
tening in the slots on the side of the tank
• Drill holes in the floor
• Properly fix the unit to the floor with dowels and screws
ca
.774
ca
.4
9
,
5
41
2
,
5
Содержание DrainLift M2/8
Страница 2: ......
Страница 4: ......
Страница 113: ...Wilo DrainLift M2 8 111 1 2 2 1 X Y X Y X Y Y Y 2 2 2 3 Y...
Страница 114: ...112 WILO SE 02 2011 2 4 Y VDE 2 5 2 6 Y X 2 7 4 3 _ Y Y Y Y X Y 4 DrainLift M2 8 EN 12050 1 EN 12056 1 DIN 1986 3...
Страница 118: ...116 WILO SE 02 2011 6 2 EN 12056 7 Y Y Y X X X Y 7 1 _ Y Y Y Y X DIN 1986 100 EN 12050 1 EN 12056...
Страница 124: ...122 WILO SE 02 2011 7 3 4 50 mm 65 mm 10 10 1a 1a 50 56 mm Y Y 1b 1b 5 mm Y 65 mm Y Y Y min 50...
Страница 125: ...Wilo DrainLift M2 8 123 7 3 5 EN 12056 4 11 10 500 x 500 x 500 mm 11 12 10 2 3 50 mm 30 45 4...
Страница 128: ...126 WILO SE 02 2011 8 WILO 8 1 Y YX Y X X Y VDE 8 2 X Y 8 2 1 Y DIP Wilo EC Drain LS2 12 Y X Y 12...
Страница 129: ...Wilo DrainLift M2 8 127 8 2 2 Y Y 2 s 12 s 8 3 X Y Y Y Y Y X Y Y X X Y X X...
Страница 131: ...Wilo DrainLift M2 8 129 1 2 WILO 11 Wilo 12 1 2 X X X 1 1 2 2 3 4 5 3 6 7 2 8 9 10 11 12 2 13 2 14 15 16 17...
Страница 203: ...Wilo DrainLift M2 8 201 1 2 p 2 1 G 2 2 2 3 h...
Страница 204: ...202 WILO SE 02 2011 2 4 2 5 2 6 2 7 4 p 3 4 DrainLift M2 8 EN 12050 1 EN 12056 1 DIN 1986 3...
Страница 205: ...Wilo DrainLift M2 8 203 m EN 12056 1 S3 15 80 12 68 45 12 6 5 5...
Страница 208: ...206 WILO SE 02 2011 6 2 EN 12056 7 7 1 1 1 2 3 DN 50 4 5 6 DN 50 DN 70 7 DN 100 DN 150 8 6 6 7 8 1 5 2 1 3 4...
Страница 210: ...208 WILO SE 02 2011 7 2 EN 12056 4 7 3 5 EN 12056 4 11 7 3 1 8 2 2 h c 11 DN 80 4 4 ca 774 ca 49 5 412 5...
Страница 214: ...212 WILO SE 02 2011 7 3 4 50 65 10 10 1a 1a 50 56 1b 1b 5 h 65 min 50...
Страница 215: ...Wilo DrainLift M2 8 213 7 3 5 EN 12056 4 11 10 500 x 500 x 500 11 12 10 2 3 50 30 45 4...
Страница 218: ...216 WILO SE 02 2011 8 Wilo 8 1 VDE h 8 2 8 2 1 Wilo EC Drain LS2 12 F N 12...
Страница 219: ...Wilo DrainLift M2 8 217 8 2 2 c h 2 12 8 3...
Страница 220: ...218 WILO SE 02 2011 9 EN 12056 4 1 Wilo Wilo 10 9 p Wilo...
Страница 222: ...220 WILO SE 02 2011 11 Wilo 12 1 2 p...
Страница 223: ...Wilo DrainLift M2 8 221 1 2 2 1 2 2 2 3 w...
Страница 224: ...222 WILO SE 02 2011 2 4 IEC VDE 2 5 p 2 6 h 2 7 4 3 h 4 DrainLift M2 8 EN 12050 1 w EN 12056 1 DIN 1986 3...
Страница 225: ...Wilo DrainLift M2 8 223 EN 12056 1 m S3 15 80 12 68 45 w 12 6 5 5 5 5 1 DrainLift M 2 8 1 DrainLift 2 2 8 Q 0 1 1 3...
Страница 228: ...226 WILO SE 02 2011 6 2 EN 12056 7 7 1 DIN 1986 100 EN 12050 1 EN 12056...
Страница 230: ...228 WILO SE 02 2011 7 2 EN 12056 4 7 3 5 EN 12056 4 11 7 3 1 8 2 2 11 DN 80 Wilo 4 4 p ca 774 ca 49 5 412 5...
Страница 234: ...232 WILO SE 02 2011 7 3 4 50 65 10 10 1a 1a 50 56 1b 1b 5 65 min 50...
Страница 235: ...Wilo DrainLift M2 8 233 7 3 5 EN 12056 4 11 10 500 x 500 x 500 3 11 12 10 2 m 3 50 30 45 4 m...
Страница 238: ...236 WILO SE 02 2011 8 Wilo 8 1 VDE p 8 2 p 8 2 1 DIP Wilo EC Drain LS2 12 F 12...
Страница 239: ...Wilo DrainLift M2 8 237 8 2 2 2 12 8 3...
Страница 241: ...Wilo DrainLift M2 8 239 1 z 2 11 Wilo p 12 1 2 1 1 2 2 3 4 5 6 7 2 8 9 10 11 12 2 13 2 14 15 16 17...