9 Supplement
WIKA Operating Instructions - Process pressure transmitter IPT-2x
Ʋ
U
B max
Depending on signal output and version of the master
sensor
Potential connections and electrical separating measures in the instrument
Electronics
Not non-floating
Reference voltage
18)
500 V AC
Conductive connection
Between ground terminal and metallic process fitting
Electrical protective measures
Housing material
Version
Protection acc. to
IEC 60529
Protection acc. to
NEMA
Plastic
Single chamber
IP66/IP67
Type 4x
Aluminium
IP66/IP67
IP66/IP68 (0.2 bar)
Type 4x
Type 6P
Stainless steel (electro-polished)
IP66/IP67
IP69K
Type 4x
-
Stainless steel (precision cast-
ing)
IP66/IP67
IP66/IP68 (0.2 bar)
Type 4x
Type 6P
Stainless steel
Transmitter for external housing IP68 (25 bar)
-
Altitude above sea level
Ʋ by default
up to 2000 m (6562 ft)
Ʋ with connected overvoltage protection
on the master sensor
up to 5000 m (16404 ft)
Pollution degree
19)
4
Protection rating (IEC 61010-1)
II
9.2 Calculation of the total deviation
The total deviation of a pressure transmitter indicates the maximum measurement error to be ex-
pected in practice. It is also called maximum practical deviation or operational error.
According to DIN 16086, the total deviation F
total
is the sum of the basic deviation F
perf
and the long-
term stability F
stab
:
F
total
= F
perf
+ F
stab
The basic deviation F
perf
consists of the thermal change of the zero signal and the output span F
T
as
well as the deviation F
Kl
:
F
perf
= √((F
T
)
2
+ (F
Kl
)
2
)
The thermal change of zero signal and output span F
T
is specified in chapter "
Technical data
". The
basic temperature error F
T
is shown in a graphic. Depending on the measuring cell version and Turn
down, this value must be multiplied with the additional factors FMZ and FTD:
F
T
x FMZ x FTD
Also these values are specified in chapter "
Technical data
".
18)
Galvanic separation between electronics and metal housing parts
19)
When used with fulfilled housing protection.