![WIKA IPT-2 Series Скачать руководство пользователя страница 40](http://html1.mh-extra.com/html/wika/ipt-2-series/ipt-2-series_operating-instructions-manual_980233040.webp)
40
6 Set up with the display and adjustment module
WIKA Operating Instructions - Process pressure transmitter IPT-2x
In this menu item you can simulate measured values. This allows the
signal path to be tested, e.g. through downstream indicating instru-
ments or the input card of the control system.
Select the requested simulation variable and set the requested value.
To deactivate the simulation, you have to push the
[ESC]
key and
confirm the message "
Deactivate simulation
" with the
[OK]
key.
Caution:
During simulation, the simulated value is output as 4 … 20 mA cur-
rent value and as digital HART signal. The status message within the
context of the asset management function is "
Maintenance
".
Note:
Without manual deactivation, the sensor terminates the simulation
automatically after 60 minutes.
In this menu item you can simulate measured values. This allows the
signal path to be tested, e.g. through downstream indicating instru-
ments or the input card of the control system.
Select the requested simulation variable and set the requested value.
To deactivate the simulation, you have to push the
[ESC]
key and
confirm the message "
Deactivate simulation
" with the
[OK]
key.
Caution:
During simulation, the simulated value is output as digital signal.
The status message along with the Asset Management function is
"
Maintenance
".
Note:
Without manual deactivation, the sensor terminates the simulation
automatically after 60 minutes.
Simulation 4 … 20 mA/
HART
Simulation bus systems