9 Supplement
WIKA Operating Instructions - Process pressure transmitter IPT-2x
1
2
0 °C
(32 °F)
40 °C
(104 °F)
80 °C
(176 °F)
105 °C
(221 °F)
85 °C
(185 °F)
Fig. 29: Temperature derating IPT-2x, version up to +105 °C (+221 °F)
1 Process temperature
2 Ambient temperature
1
2
0 °C
(32 °F)
40 °C
(104 °F)
80 °C
(176 °F)
150 °C
(302 °F)
85 °C
(185 °F)
Fig. 30: Temperature derating IPT-2x, version up to +150 °C (+302 °F)
1 Process temperature
2 Ambient temperature
SIP process temperature (SIP = Sterilization in place)
Vapour stratification for 2 h
13)
+150 °C (+302 °F)
Process pressure
Permissible process pressure
see specification "
Process pressure
" on the type label
Mechanical stress
Version
Without cooling zone
With cooling zone
All housing ver-
sions
Double cham-
ber stainless steel
housing
All housing ver-
sions
Double cham-
ber stainless steel
housing
Vibration resist-
ance 1 to 4 g at
5 … 200 Hz accord-
ing to EN 60068-2-6
(vibration with reso-
nance)
4 g (GL characteris-
tics 2)
0.7 g (GL character-
istics 1)
4 g (GL characteris-
tics 2)
0.7 g (GL character-
istics 1)
Shock resistance
2.3 ms according to
EN 60068-2-27 (me-
chanical shock)
50 g
50 g
20 g
13)
Instrument configuration suitable for vapour