4 Mounting
WIKA Operating Instructions - Process pressure transmitter IPT-2x
4.5 Differential pressure measurement
The master/slave combination is suitable for differential pressure
measurement
Take note of the following instructions for the measurement setup, for
example in gases:
•
Mount the instruments above the measuring point
Possible condensation can then drain off into the process line.
1
2
Fig. 12: Measurement setup for differential pressure measurement of gases in
pipelines
1 IPT-2x
2 IPT-2x, slave sensor
4.6 Interface measurement
The master/slave combination is suitable for interface measurement
Requirements for a functioning measurement are:
•
Vessel with changing level
•
Products with steady density
•
Interface always between the measurement points
•
Total level always above the upper measurement point
The mounting distance h of the two sensors should be at least 10 %,
better 20 %, of the final value of the sensor measuring range. A bigger
distance increases the accuracy of the interface measurement.
Measurement setup
Measurement setup