4 Mounting
WIKA Operating Instructions - Process pressure transmitter IPT-2x
Differential pressure on orifice: 50 mbar = 0.050 bar
Total pressure: 0.8 bar + 0.05 bar = 0.85 bar
Instrument selection
Nominal measuring range Master: 1 bar
Nominal measuring range Slave: 1 bar
Turn Down: 1 bar/0.050 bar = 20 : 1
The measuring result (level, pressure difference) as well as meas-
ured value Slave (static or superimposed pressure) are output by the
sensor. Depending on the instrument version, output as 4 … 20 mA
signal or digitally via HART, Profibus PA or Foundation Fieldbus.
4.4 Level measurement
The master/slave combination is suitable for level measurement in a
pressurized vessel
Keep the following in mind when setting up the measuring system:
•
Mount the master sensor below the min. level
•
Do not mount the master sensor close to the filling stream or
emptying area
•
Mount the master sensor so that it is protected against pressure
shocks from the stirrer
•
Mount the slave sensor above the max. level
1
2
Fig. 11: Measurement setup, level measurement in pressurized vessel
1 IPT-2x
2 IPT-2x, slave sensor
Output measured values
Measurement setup