39
6 Set up with the display and adjustment module
WIKA Operating Instructions - Process pressure transmitter IPT-2x
6.1.2 Display
In this menu item, you define which measured value is displayed.
The default setting for the displayed value is "
Differential pressure
".
In this menu item you define the number of decimal positions with
which the measured value is displayed.
The default setting for the display format is "
Automatic
".
In this menu item, you define which measured value is displayed.
The default setting for the displayed value is "
Differential pressure
".
In this menu item you define the number of decimal positions with
which the measured value is displayed.
The default setting for the display format is "
Automatic
".
6.1.3 Diagnostics
The respective min. and max. measured values for the differential
pressure and static pressure are stored in the sensor. In menu item
"
Peak value, pressure
", both values are displayed.
In another window you can carry out a reset of the peak values
separately.
Display value 1 and 2 -
4 … 20 mA
Display format 1 and 2
Display value 1 and 2 -
bus systems
Display format 1 and 2
Peak value, pressure