5
Item
Explanation
Anti-smashing
Interface
Infrared Photocell: boom will lift up when short circuiting
“Infrared photocell interface” and “GND” during boom down.
Loop Detector: boom will lift up when short circuiting “loop
detector interface” and “GND” during boom down; in up limit
position, boom will fall down automatically after these two
interfaces disconnected.
RS485
communication
interface
It is used for controlling the barrier gate or checking the status of
the barrier gate by computer or system; also used for online
controlling the paired barrier gates synchronously.
Limit
Relay
Output
Interface
It is used for the system to checking the status of the barrier gate
by the opening and closing times; users can also change to other
output modes via option 4 of the advanced menu.
DC12V Power
Output
Provide 1A current output, available for radar or small light strips.
Interface
for
R&G lights
Available to connect with R&G lights, to indicate the working
status of the barrier gate.
Buttons
of
Mater Motor
The 4 buttons have two working status: normal working status
and menu setting status, the function of normal working status is
that “
▲
” is the opening function, “
▼
” is the closing function, (in
normal working status of slave motor also link-able to open and
close), “
■
” is the stopping function, “
三
” is the setting function
which is invalid when it is short pressed under normal working
status; Long press “
三
” for 2 seconds to enter the menu setting
status. In the menu setting status, “
▲
” and “
▼
” are used to adjust
menu items or parameters, “
■
” is to cancel the set value or exit
the menu setting status, “
三
” is used to enter the next menu or
save the set value. (Note: These buttons can only set the menu of
master motor)