4.4.8. Valid time of loop detector signal
In the process of opening or up limit position, the duration time of the loop detector
signal needs to exceed the setting time, and the auto-closing action will be executed
after the loop detector signal disappears, avoiding that the loop detector signal is too
short and triggers the auto-closing action to hit the vehicles. The default time is
200ms. Range: 100ms-900ms.
4.4.9. Beep of Loop detector signal
There is loop detector signal (there is vehicle on the loop wire) when boom is at up
limit position, the buzzer will emit a hint tone. "ON" has a sound, and "OFF" has no
sound. “ON” is default.
4.4.10. Failure angle of loop detector anti-smashing
During the closing process, when the boom arrives at the setting angle from the
horizontal level, it will not respond to the signal of loop detector, to prevent vehicle
from being followed by other vehicles, and can also prevent the misoperation of the
loop detector from triggering the opening of the barrier gate. The default value is 5
degrees.
4.4.11. Failure angle on obstacle
During the closing process, when the boom arrives at the setting angle from the
horizontal level, if the boom meets on obstacle, it will not respond to barrier gate
opening. The default value is 10 degrees.
4.4.12. Switching angle of R&G light
When the boom opens to the setting angle, the relay of R&G light will close. The
default value is 60 degrees.
4.4.13. Wire control signal type measurement
"Infrared photocell", "loop detector/radar” and "stop" signals of the wire control
interface can be set to normal open input and normal close input, and the default is
normal open input.
4.5. Controller Parameter Setting of Slave Motor
Long press “
” button for 2 seconds to enter the regular menu setting status. The
LED digital tube will display “F-XX”. Select menu items by short press or long press