Dimmer C: Scene function
Dimmer D: Scene function
If the scene function is activated, the following group objects ap-
pear:
Group Object Dimmer A
Type KNX
Size
Direction
GO 178 Dimmer A: Scene - Activ./Lrn.
18.001
1 Byte
From KNX
Group Object Dimmer B
Type KNX
Size
Direction
GO 238 Dimmer B: Scene - Activ./Lrn.
18.001
1 Byte
From KNX
Group Object Dimmer C
Type KNX
Size
Direction
GO 298 Dimmer C: Scene - Activ./Lrn.
18.001
1 Byte
From KNX
Group Object Dimmer D
Type KNX
Size
Direction
GO 358 Dimmer D: Scene - Activ./Lrn.
18.001
1 Byte
From KNX
Fade time on activation of scene
Here the period can be set in which the received scene is
dimmed to. The period refers to a complete dimming process of
0-100%.
Scene 1-16
These parameters can be used to configure the reaction of the
channel when the respective scene is received.
It is available:
-
No reaction
-
Dimming value
The output is switched to the set dimming value if the
scene of the corresponding number was received.
-
Learnable
With the help of a scene control telegram, the current
state at the output for the respective scene can be
saved here. Thus the scene can be adapted by the
user without ETS download.
Number
With this parameter any scene number between 1 and 64 can be
assigned to the scene. No scene numbers may be assigned
twice.
H.
Dimmer A: Slumber function
Dimmer B: Slumber function
Dimmer C: Slumber function
Dimmer D: Slumber function
If the slumber function is active, the following objects are visible:
Group Object Dimmer A
Type KNX
Size
Direction
GO 181 Dimmer A: Slumber function -
Trigger
1.001
1 Bit
From KNX
Group Object Dimmer B
Type KNX
Size
Direction
GO 241 Dimmer B: Slumber function -
Trigger
1.001
1 Bit
From KNX
Group Object Dimmer C
Type KNX
Size
Direction
GO 301 Dimmer C: Slumber function -
Trigger
1.001
1 Bit
From KNX
Group Object Dimmer D
Type KNX
Size
Direction
GO 361 Dimmer D: Slumber function -
Trigger
1.001
1 Bit
From KNX
Target value while switching on the slumber function
This value is reached by the channel after completion of the dim-
ming process after receiving an ON telegram via object 181, 241,
301 or 361.
Target value while switching off the slumber function
This value is reached by the channel after completion of the dim-
ming process after receiving an OFF telegram via object 181,
241, 301 or 361.
Fade time on 1. ON telegram (1. button press)
This fade time is used to dim to the target value for switching on
after the 1. button press. The period refers to a complete dim-
ming process of 0-100%.
Fade time on 2. ON telegram (2. button press)
This fade time is used to dim to the target value for switching on
after the 2. button press. The period refers to a complete dim-
ming process of 0-100%.
Fade time on 1. OFF telegram (1. button press)
This fade time is used to dim to the target value for switching off
after the 1. button press. The period refers to a complete dim-
ming process of 0-100%.