2019 WEINZIERL ENGINEERING GmbH
Page 14/41
The output values are fixed for the "Linear" and "Logarithmic"
dimming curves, and can be freely configured for the "User-de-
fined" curves.
If a dimming value of 0% is reached, the channel always
switches off.
Adjustment red
Adjustment green
Adjustment blue
Adjustment white
The PWM value of the color calculated by the dimming curve is
additionally scaled with this value. "Adjustment white" is only
available in RGBW configuration.
H.
RGB A: Scene function
If the scene function is activated, the following group object ap-
pears:
Group Object
Type KNX
Size
Direction
GO 40 RGB A: Scene - Activ./Lrn.
18.001
1 Byte
From KNX
Fade time on activation of scene
Here the period can be set in which the received scene is
dimmed to. The period refers to a complete dimming process of
0-100%.
Scene 1-16
These parameters can be used to configure the reaction of the
channel when the respective scene is received.
It is available:
-
No reaction
-
Color
The output is switched to the set color value if the
scene of the corresponding number was received.
-
Learnable
With the help of a scene control telegram, the current
state at the output for the respective scene can be
saved here. Thus the scene can be adapted by the
user without ETS download.
Number
With this parameter any scene number between 1 and 64 can be
assigned to the scene. No scene numbers may be assigned
twice.
I.
RGB A: Slumber function
If the slumber function is active, the following object is visible:
Group Object
Type KNX
Size
Direction
GO 43 RGB A: Slumber function - Trig-
ger
1.001
1 Bit
From KNX
Target color while switching on the slumber function
This color is reached by the channel after completion of the dim-
ming process after receiving an ON telegram via object 43.
Target color while switching off the slumber function
This color is reached by the channel after completion of the dim-
ming process after receiving an OFF telegram via object 43.
Fade time on 1. ON telegram (1. button press)
This fade time is used to dim to the target color for switching on
after the 1. button press. The period refers to a complete dim-
ming process of 0-100%.
Fade time on 2. ON telegram (2. button press)
This fade time is used to dim to the target color for switching on
after the 2. button press. The period refers to a complete dim-
ming process of 0-100%.
Fade time on 1. OFF telegram (1. button press)
This fade time is used to dim to the target color for switching off
after the 1. button press. The period refers to a complete dim-
ming process of 0-100%.
Fade time on 2. OFF telegram (2. button press)
This fade time is used to dim to the target color for switching off
after the 2. button press. The period refers to a complete dim-
ming process of 0-100%.
J.
RGB A: Lock function
0%
10%
20%
30%
40%
50%
60%
70%
80%
90%
100%
0% 10% 20% 30% 40% 50% 60% 70% 80% 90% 100%