By on/off telegram
-
When receiving a parameterized scene number
When a step is activated, a value can be dimmed to or a scene
number can be sent, and a step or a whole sequence of steps
can be repeated cyclically.
The following objects are available for the general control of the
sequencer:
Group Object Dimmer A
Type KNX
Size
Direction
GO 193 Dimmer A: Sequence suspend -
Suspend/Resume
1.001
1 Bit
From KNX
GO 194 Dimmer A: Sequence on/off -
Switch
1.001
1 Bit
From KNX
Group Object Dimmer B
Type KNX
Size
Direction
GO 253 Dimmer B: Sequence suspend -
Suspend/Resume
1.001
1 Bit
From KNX
GO 254 Dimmer B: Sequence on/off -
Switch
1.001
1 Bit
From KNX
Group Object Dimmer C
Type KNX
Size
Direction
GO 313 Dimmer C: Sequence suspend -
Suspend/Resume
1.001
1 Bit
From KNX
GO 314 Dimmer C: Sequence on/off -
Switch
1.001
1 Bit
From KNX
Group Object Dimmer D
Type KNX
Size
Direction
GO 373 Dimmer D: Sequence suspend -
Suspend/Resume
1.001
1 Bit
From KNX
GO 374 Dimmer D: Sequence on/off -
Switch
1.001
1 Bit
From KNX
The following parameters determine the general behavior of the
sequencer:
Steps of sequencer
Number of steps (0...32) to be used
Resume sequence after man. operation
An activated sequence can always be interrupted or continued
via object 193, 253, 313 or 373 an ON telegram interrupts the
sequence, and with an OFF telegram it is continued.
A sequence is also interrupted after manual operation, i.e. after
commands for dimmer, automatic mode, slumber or scene func-
tion.
In addition, this parameter determines how an interrupted se-
quence can still be continued:
-
Only by object
The sequence can only be continued by object 193,
253, 313 or 373.
-
After off-time
The sequence is continued after the set off-time.
-
On next activated step
The sequence is continued with the next activated
step, the next step can be activated by object or time-
controlled.
Off-time
Only visible if the sequence is to be continued after off-time, with
this parameter the off-time can be configured.
Step after man. operation
This step is executed when resuming after manual operation, the
function of the set step is always executed, regardless of its oth-
erwise set starting conditions.
Polarity of object “Sequence on/off“
This parameter can be used to set the telegram value with which
the sequence can be switched on and off via object 194, 254,
314 or 374. If the sequence is switched off, any further activation
of a step is disabled.
Behavior on switching on
Here it is determined how the sequencer behaves when
switched on by object 194, 254, 314 or 374:
-
No reaction
No function is executed, the sequencer waits for steps
to be activated.
-
Step x
The function of the step is executed (independent of
the other set start conditions of the step), the se-
quence is then continued according to its configuration
from this step onwards.
Switching on also reactivates a sequence interrupted by manual
operation.
Behavior on switching off
Here it is determined how the sequencer behaves when
switched off by object 194, 254, 314 or 374:
-
Complete actual step
If the sequencer is in a dimming process, it is com-
pleted.
-
Step x
The function of the step is executed (independent of
the other set start conditions of the step).
-
Stop immediately
If the sequencer is in a dimming process, it is stopped.
Apart from the set behavior when switching off, any further acti-
vation of a step after switching off is disabled until the sequencer
is switched on again by object 194, 254, 314 or 374.
Step 1-32
When a step is activated, its parameters for configuration ap-
pear.
In the text box at the top right with the content "Step x", you can
enter your own name for the step. This designation serves for
better orientation of the user and has no influence on the func-
tion of the step.
Start by time
This parameter is used to configure a temporal start condition of
the step.
-
Disabled
Start condition not used
-
Start at a fixed time of day
Here the time of day at which the step should start can
be entered. When using this start condition, the current
time must have been received via the following object:
Group Object
Type KNX
Size
Direction
GO 5 Time of Day - Set
10.001
3 Byte
From KNX
If no valid time was received by object 5, all
start conditions at fixed times of day are not
active.