2019 WEINZIERL ENGINEERING GmbH
Page 24/41
Fade time while decreasing brightness with object
This fade time is active when the brightness is decreased by rel-
ative dimming with object 19 or 99. The period refers to a com-
plete dimming process of 0-100%.
Object change Brightness (abs.)
The following objects are used to control the brightness via dim-
ming value, if activated via parameters:
Group Object TW A
Type KNX
Size
Direction
GO 20 TW A: Brightness dimming abs. -
Set value
5.001
1 Bit
From KNX
Group Object TW B
Type KNX
Size
Direction
GO 100 TW B: Brightness dimming abs.
- Set value
5.001
1 Bit
From KNX
Minimal value for changing brightness value by object
This parameter can be used to configure which minimum bright-
ness can be achieved via object 20 or 100. If a value below the
minimum value is received, the dimmer is controlled with the
minimum value. If a value >0% is set here, the following parame-
ter is also visible:
Switch off dimmer with telegram value 0%
Here it is to select whether the dimmer is switched off when a
value of 0% is received.
Maximal value for changing brightness value by object
This parameter can be used to configure which maximum bright-
ness can be achieved via object 20 or 100. If a value above the
maximum value is received, the dimmer is controlled with the
maximum value.
Fade time while increasing brightness with object
This fade time is active when the brightness is increased by re-
ceiving values via object 20 or 100. The period is related to a
complete dimming process of 0-100%.
Fade time while decreasing brightness with object
This fade time is active when the brightness is decreased by re-
ceiving values via object 20 or 100. The period is related to a
complete dimming process of 0-100%.
E.
TW A: Staircase function
TW B: Staircase function
This parameter page can be used to implement a staircase func-
tion with optional orientation light. The staircase function can be
overridden by the lock function. It has the following objects:
Group Object TW A
Type KNX
Size
Direction
GO 11 TW A: Staircase function - Trig-
ger
1.010
1 Bit
From KNX
GO 21 TW A: Day/Night - Switch
1.001
1 Bit
From KNX
Group Object TW B
Type KNX
Size
Direction
GO 91 TW A: Staircase function - Trig-
ger
1.010
1 Bit
From KNX
GO 101 TW A: Day/Night - Switch
1.001
1 Bit
From KNX
Day mode is triggered with an OFF telegram on object 21 or 101,
night mode with an ON telegram. After a restart, the device is in
day mode.
Color temperature on switching on the staircase function
(day)
This color temperature is used in day mode when the staircase
function is switched on by ON telegram to object 21 or 101.
Brightness on switching on the staircase function (day)
This brightness is used in day mode when the staircase function
is switched on by ON telegram to object 21 or 101.
Color temperature on switching on the staircase function
(night)
This color temperature is used in night mode when the staircase
function is switched on by ON telegram to object 21 or 101.
Brightness on switching on the staircase function (night)
This brightness is used in night mode when the staircase func-
tion is switched on by ON telegram to object 21 or 101.
Fade time for switching on
This fade time is active when the staircase function is switched
on by ON telegram to object 21 or 101. The period refers to a
complete dimming process of 0-100%.
Delay time for staircase function
After the delay time has elapsed, the dimmer is dimmed to the
switch-off or orientation light color, depending on the parameter
setting.
Reaction on ON telegram
This parameter determines the behavior after switching on the
staircase function via ON telegram to object 21 or 101: With the
"Switch on" setting, the channel remains switched on after ON
telegram until the delay time is started via OFF telegram. In the