2019 WEINZIERL ENGINEERING GmbH
Page 20/41
The following objects are available for dimming brightness using
relative dimming commands, if activated via parameters:
Group Object TW A
Type KNX
Size
Direction
GO 12 TW A: Color temperature via
brightness dimming rel. - Brighter/Darker
3.007
4 Bit
From KNX
Group Object TW B
Type KNX
Size
Direction
GO 92 TW B: Color temperature via
brightness dimming rel.- Brighter/Darker
3.007
4 Bit
From KNX
Minimal brightness while changing with object
This parameter can be used to set the minimum brightness that
can be achieved by relative dimming. If the current brightness is
below the minimum value, the brightness cannot be reduced via
object 12 or 92.
Maximal brightness while changing with object
This parameter can be used to set the maximum brightness that
can be achieved by relative dimming. If the current brightness is
above the maximum value, the brightness cannot be increased
via object 12 or 92.
Fade time while increasing brightness with object
This fade time is active when the brightness is increased by rela-
tive dimming with object 12 or 92. The period refers to a com-
plete dimming process of 0-100%.
Fade time while decreasing brightness with object
This fade time is active when the brightness is decreased by rel-
ative dimming with object 12 or 92. The period refers to a com-
plete dimming process of 0-100%.
Object set value Brightness (abs.)
The following objects are used to control the brightness via dim-
ming value, if activated via parameters:
Group Object TW A
Type KNX
Size
Direction
GO 13 TW A: Color temperature via
brightness dimming abs. - Set value
5.001
1 Byte
From KNX
Group Object TW B
Type KNX
Size
Direction
GO 93 TW B: Color temperature via
brightness dimming abs. - Set value
5.001
1 Byte
From KNX
Minimal value for changing brightness by object
This parameter can be used to configure which minimum bright-
ness can be reached via object 13 or 93. If a value below the
minimum value is received, the dimmer is controlled with the
minimum value. If a value >0% is set here, the following parame-
ter is also visible:
Switch off dimmer with telegram value 0%
Here it is to select whether the dimmer is switched off when a
value of 0% is received.
Maximal value for changing brightness by object
This parameter can be used to configure the maximum bright-
ness that can be achieved via object 13 or 93. If a value above
the maximum value is received, the dimmer is controlled with the
maximum value.
Fade time while increasing brightness with object
This fade time is active when the brightness is increased by re-
ceiving values via object 13 or 93. The period is related to a
complete dimming process of 0-100%.
Fade time while decreasing brightness with object
This fade time is active when the brightness is decreased by re-
ceiving values via object 13 or 93. The period is related to a
complete dimming process of 0-100%.
C.
TW A: Color temperature
TW B: Color temperature
Object Color Temperature on/off
The following objects are available for switching the color tem-
perature, if they have been activated via parameters:
Group Object TW A
Type KNX
Size
Direction
GO 14 TW A: Color temperature on/off -
Switch
1.001
1 Bit
From KNX
Group Object TW B
Type KNX
Size
Direction
GO 94 TW B: Color temperature on/off -
Switch
1.001
1 Bit
From KNX
Behavior on ON telegram
This parameter can be used to configure the behavior when
switching on via the respective object.
It is available:
-
No reaction
-
Dim to fix color temperature