Minimal value while changing color temperature with object
This parameter can be used to configure which minimum color
temperature can be reached via objects 16 and 96. If a value be-
low the minimum value is received, the dimmer is controlled with
the minimum value.
Maximal value while changing color temperature with object
This parameter can be used to configure the maximum color
temperature that can be reached via objects 16 and 96. If a
value above the maximum value is received, the dimmer is con-
trolled with the maximum value.
Fade time while changing color temperature with object
This fade time is active when the color temperature is changed
by receiving a value via object 16 and 96. The period refers to a
complete dimming process of 0-100%.
Object set Color Temperature via scaling value (abs.)
The following objects are used to control the color temperature
by scaling value, if they have been activated via parameters:
Group Object TW A
Type KNX
Size
Direction
GO 17 TW A: Color temperature dim-
ming abs. - Set value
5.001
1 Byte
From KNX
Group Object TW B
Type KNX
Size
Direction
GO 97 TW B: Color temperature dim-
ming abs. - Set value
5.001
1 Byte
From KNX
Color temperature on telegram value 0%
This parameter can be used to configure which color tempera-
ture is set when receiving 0% via objects 17 and 97.
Color temperature on telegram value 100%
This parameter can be used to configure which color tempera-
ture is set when receiving 100% via objects 17 and 97
If a value between 0-100% is received, the color temperature is
calculated and output linearly on basis of the set limit values.
Fade time while changing color temperature with object
This fade time is active when the color temperature is changed
by receiving a value via object 17 and 97. The period refers to a
complete dimming process of 0-100%.
Adjust brightness with color temperature objects, when
brightness 0%
If the current brightness is 0% and the color temperature is
changed via one of the objects in the parameter block Color
Temperature, the brightness is dimmed to the set brightness at
the same time. If the current brightness is >0%, this parameter
has no effect on the brightness.
If this parameter is not used, a change in the color
temperature has no visible effect if the current bright-
ness is 0%.
Fade time
This fade time is active if the current brightness is 0% and the
color temperature is changed via one of the objects in the pa-
rameter block. The period refers to a complete dimming process
of 0-100%.
D.
TW A: Brightness
TW B: Brightness
Object Brightness on/off
The following objects are available for switching the brightness, if
they have been activated via parameters:
Group Object TW A
Type KNX
Size
Direction
GO 18 TW A: Brightness on/off - Switch
1.001
1 Bit
From KNX
Group Object TW B
Type KNX
Size
Direction
GO 98 TW B: Brightness on/off - Switch
1.001
1 Bit
From KNX
Behavior on ON telegram (when Brightness 0%)
If the current brightness is 0%, this parameter can be used to
configure the behavior when switching on via object 18 or 98.
It is available:
-
No reaction
-
Dim to fix value
-
Dim to last value before switching off