2019 WEINZIERL ENGINEERING GmbH
Page 21/41
Color temperature on ON telegram
This color temperature is activated by ON telegram via object 14
or 94 if the parameters are suitable.
Fade time on ON telegram
This fade time is active when an ON telegram is received. The
period refers to a complete dimming process of 0-100%.
Behavior on OFF telegram
This parameter describes the behavior of the dimmer when an
OFF telegram is received via object 14 or 94.
It is available:
-
No reaction
-
Dim to fix color temperature
Color temperature on OFF telegram
This color temperature is activated by OFF telegram via object
14 or 94 if the parameters are suitable.
Fade time on OFF telegram
This fade time is active when an OFF telegram is received. The
period refers to a complete dimming process of 0-100%.
Day/night switching
When using this function, the following objects are visible for
switching between day/night mode:
Group Object TW A
Type KNX
Size
Direction
GO 21 TW A: Day/Night - Switch
1.001
1 Bit
From KNX
Group Object TW B
Type KNX
Size
Direction
GO 101 TW B: Day/Night - Switch
1.001
1 Bit
From KNX
Day mode is triggered with an ON telegram on the respective ob-
ject, night mode with an OFF telegram. After a restart, the device
is in day mode.
Telegrams on object 21 or 101 affect all activated
day/night switches of the TW channel.
In addition, it can be determined when the values become active
after receiving a telegram on these objects, it is available:
-
Disabled
-
Switch on day/night telegram
Immediately after reception of day/night switching, it is
dimmed to the active value according to the last
switch-on/switch-off received via object 14 or 94.
-
Switch on next on/off telegram
The currently active value is not used until the next
switch on/off telegram via object 14 or 94.
There is a separate switch-on and switch-off value for night
mode in the parameters, in day mode the always visible values
are used.
Color temperature on ON telegram (night)
If the dimmer is in night mode, this value is activated by ON tele-
gram via object 11or 91 and suitable parameterization.
Color temperature on OFF telegram (night)
If the dimmer is in night mode, this value is activated by OFF tel-
egram via object 11 or 91 and suitable parameterization.
Fade time for day/night switching
This fade time is only active if switching on day/night telegram is
used. If switching on next on/off telegram is used, the regular
fade time of the respective on or off telegram is active. The pe-
riod refers to a complete dimming process of 0-100%.
Object change Color Temperature (rel.)
To change the color temperature by relative dimming com-
mands, the following objects are available, if activated via pa-
rameters:
Group Object TW A
Type KNX
Size
Direction
GO 15 TW A: Color temperature dim-
ming rel. - Increase/Decrease
3.007
4 Bit
From KNX
Group Object TW B
Type KNX
Size
Direction
GO 95 TW B: Color temperature dim-
ming rel. - Increase / Decrease
3.007
4 Bit
From KNX
Minimal color temperature while changing with object
This parameter can be used to set which minimum color temper-
ature can be achieved by relative dimming. If the current color
temperature is below the minimum value, the color temperature
cannot be reduced via object 15 or 95.
Maximal color temperature while changing with object
This parameter can be used to set the maximum color tempera-
ture that can be achieved by relative dimming. If the current satu-
ration is above the maximum value, the color temperature cannot
be increased via object 15 or 95.
Fade time while changing color temperature with object
This fade time is active when the color temperature is changed
by relative dimming with object 15 or 95. The period refers to a
complete dimming process of 0-100%.
Object set Color Temperature via temperature value (abs.)
The following objects are used to control the color temperature
via the temperature value, if they have been activated via param-
eters:
Group Object TW A
Type KNX
Size
Direction
GO 16 TW A: Color temperature value
abs. - Set value
7.600
2 Byte
From KNX
Group Object TW B
Type KNX
Size
Direction
GO 96 TW B: Color temperature value
abs. - Set value
7.600
2 Byte
From KNX