Part number 550-142-085/0712
– 59 –
WM97+
gas
-
fired
water
boiler
—
Boiler Manual
Legend — Figure 66
The boiler internal primary/secondary by-pass valve must be CLOSED
for multiple boiler installations
piped as shown in this manual. This allows the boiler internal circulator to circulator water to and from the manifolds.
1
Flow/check valve (integral to each
boiler internal circulator)
2
Isolation valves (when used)
3
Cap
4
Easy-Fit® Manifold (supply) —
layout and size per page 55
5
Easy-Fit® Manifold (return) —
layout and size per page 55
6a
Heating system circulator (ex-
changer tube-side)
6b
Heat exchanger shell-side circulator
7
Expansion tanks (diaphragm type)
8
System air eliminator
9
System automatic air vent
13
Cold water supply connections
17
Boiler circulator — circulates water
between boiler and Easy-Fit® Manifolds
18
Heating system supply
19
Heating system return
20
Boiler relief valve and discharge piping,
installed per WM97+ Boiler Manual
Notes:
1. Contact heat exchanger manufacturer for heat exchanger
shell-side and tube-side piping and circulator require-
ments. Tube-side flow and temperatures must meet
heating system requirements.
2. Contact heat exchanger manufacturer for sizing heat
exchanger.
3. Heat exchanger shell-side circuit requires its own expan-
sion tank as shown.
4. Heating system circuit requires its own expansion tank,
as shown, plus its own relief valve set to protect heating
system and heat exchanger piping and components.
5. When individual isolation valves are used, individual
boiler and level controls may be required.
Figure 66
Piping layout — typical piping for multiple WM97+ boilers, using isolation exchanger (shown using
WM97+155 boilers — adjust boiler connections as required for other boiler models)
Use isolation heat
exchanger for:
1.
Large volume systems with high
mineral content in water.
2.
Systems exposed to untreated
quantities of makeup water.
3.
Old systems severely contami-
nated with scale and rust buildup
inside piping and heat distribu-
tion units.
4.
Process applications.
5.
Commercial service water ap-
plications.
6.
High water pressure applications,
requiring pressure relief setting
in heating system more than 30
PSIG (tall buildings). See notes
below.
Multiple boiler installations
(continued)
Heat exchanger type —
The illustration shows a
shell and tube exchanger.
Other exchanger types
may be used if suitable for
the system water condi-
tions.