Part number 550-142-085/0712
WM97+
gas
-
fired
water
boiler
—
Boiler Manual
– 86 –
Startup — fill the system
(continued)
Freeze protection (if used)
Follow these guidelines to prevent pos-
sibility of severe personal injury, death
or substantial property damage:
Use only the products listed by Weil-
McLain for use with this boiler. See
page 117 for information.
Thoroughly flush any system that
has used glycol
before installing the
new WM97+ boiler.
Review the material safety data
sheets (MSDS)
are available online.
The MSDS contains information on po-
tential hazards and first aid procedures
for exposure or ingestion.
Check antifreeze inhibitor level at
least annually
. Glycol concentration
and inhibitor levels may change over
time. Add antifreeze to increase con-
centration if necessary. Add inhibitor
as needed to bring to acceptable level,
using inhibitor test kit to verify.
In addition to antifreeze and inhibitor,
use and maintain minimum level of
Sentinel X100 inhibitor as directed on
this page.
If using freeze protection fluid with
automatic fill,
install a water meter to
monitor water make-up
. Freeze pro-
tection fluid may leak before the water
begins to leak, causing concentration
to drop, reducing the freeze protection
level.
DO NOT exceed 50% antifreeze
by volume
. Antifreeze moves more
sluggishly than water and can interfere
with heat transfer. At antifreeze concen-
trations higher than 50%, sludge can
develop in the boiler, potentially causing
damage to the heat exchanger.
Clean the system before filling
.
Always drain and flush the system
thoroughly before filling with antifreeze.
Sludge, iron oxide deposits and other
sediment in the system inhibit flow and
can cause rapid breakdown of inhibi-
tors.
Use only antifreeze recommended by
Weil-McLain.
Weil-McLain provides information for
application of the antifreeze products
listed in this document only for use in
Weil-McLain WM97+ boilers. Do not
apply these products or instructions
for other applications. Local codes may
require a backflow preventer or actual
disconnection from city water supply.
and proceed with the next zone. Follow this procedure until all zones
are purged. Follow the same procedure to purge air from the boiler
and its internal piping.
7. Close the quick-fill water valve and purge valve and remove the hose.
Open all isolation valves. Watch that system pressure rises to correct
cold-fill pressure.
8. After the system has operated for a while, eliminate any residual air by
using the manual air vents located throughout the system.
9. If purge valves are not installed in system, open manual air vents in
system one at a time, beginning with lowest floor. Close vent when
water squirts out. Repeat with remaining vents.
10. Open automatic air vent (diaphragm-type or bladder-type expansion
tank systems only) one turn.
11. Starting on the lowest floor, open air vents one at a time until water
squirts out.
12. Repeat with remaining vents.
13. Refill to correct pressure.
Use X100 inhibitor supplied with boiler
1. The WM97+ boiler is shipped with Sentinel X100 inhibitor and Sen-
tinel X100 Quick Test Kit. See Repair Parts at the end of this manual
for re-ordering information.
2. After filling the system as directed in these instructions, use a caulking
gun to inject the X100 inhibitor into the system, following the instruc-
tions on the tube.
3. Inject all of the inhibitor supplied with the boiler. Allow time for the
water to circulate and mix. Then check the inhibitor level. Add addi-
tional inhibitor if necessary.
Check/verify water chemistry
1. The system may have residual substances that could affect water
chemistry.
2. After the system has been filled and leak tested, verify water pH and
chloride concentrations are acceptable.
3. Verify antifreeze concentration, if used.
4. Follow the instructions on the Sentinel test kit to sample the system
water and verify inhibitor concentration.
Check inhibitor concentration annually
1. Test the pH of a sample of system water at least annually. The pH of
the water mixture must be between 7.0 and 8.5. (Or use the Sentinel
inhibitor test kit to check concentration.)
2. If pH is outside this range (or inhibitor test kit indicates low level), the
inhibitor level may not be sufficient to prevent corrosion.
3. Test antifreeze concentration.
Test antifreeze concentration at least annually. If concentra-
tion is low, add antifreeze or drain system and refill with
correct mixture.
4. Follow instructions on antifreeze container to determine the amount
of antifreeze needed.
DO NOT
exceed 50% by volume concentration
of antifreeze.
5. Check inhibitor level after adjustments are made.
Содержание WM97+110
Страница 1: ......