Part number 550-142-085/0712
WM97+
gas
-
fired
water
boiler
—
Boiler Manual
– 104 –
Troubleshooting
(continued)
Display
Condition
Diagnostics
Corrective Action(s)
Nothing shown
on display
screen and
boiler will not
respond to call
for heat
Control is not receiving 24V
power
Check wiring for short circuit or
incorrect wiring.
Correct wiring per wiring diagram including connection of transformer
to the WM97+ control.
Check 3-amp low voltage fuse
on WM97+ control shown on
page 101
.
Replace fuse with proper part found in replacement part section of this
manual. If fuse blows again recheck wiring per diagram.
Check transformer connection
to the WM97+ control per
wiring diagram. Check for 24V
output of transformer.
Replace transformer if it is is receiving 120Vac, but not outputting 24Vac.
Nothing
is shown
in display
screen and no
other boiler
components are
operating
Control is not receiving 120V
power
Check service switch and/or
circuit breaker to boiler turned
is on.
Turn on service switch to power boiler.
Is there 120 Volts at the service
switch?
Troubleshoot and correct the power supply to the service switch.
Is the WM97+'s ON/OFF POWER
SWITCH located on top of the
boiler
Turn the WM97+'s power switch to ON.
Check for 120 volts at the line
voltage terminal block located
inside the top left electrical
compartment
Correct wiring inside the control pod using the wiring diagram in this
manual.
Inspect 12-amp fuse as shown
on
page 101
. Replace if
necessary.
Replace the fuse with proper part found in the replacement part section
of this manual. If fuse blows again recheck wiring per diagram.
Nothing is
shown on
display screen,
but boiler is
operating
Occurs if the communication
is lost from the WM97+
control to the display.
Check for loose connections
and proper pin alignment/
engagement on the WM97+
control's plug P9 and the back
of the display circuit board.
Check for continuity on the wire harness from the display to the WM97+
control. See repair parts section for proper replacement part.
Cycle power off and on using
boiler power switch and check
for operation.
Replace with new display module. See repair parts section for proper
replacement part.
TEMP RISE TOO
QUICKLY
Occurs if supply water
temperature in heat
exchanger rises faster than
2ºF per second during the
first two minutes the burner
is on.
Automatically resets after 1
minute delay or using manual
reset on display.
Manual reset is necessary after 5
automatic resets have occurred
during the same Priority heat
demand. Reset using manual
reset screen on display
Verify water pipe is installed correctly per instructions in this manual.
Verify proper circulator and speed for boiler size and system
requirements.
See message displayed TEMPERATURE SENSOR and follow procedure for
loose connections.
SUPPLY 58F >
RETURN
Boiler Out temperature
has exceeded the Boiler In
temperature by more than
58ºF
Automatically resets after 30
second delay or using manual
reset on display.
Verify water pipe is installed correctly per instructions in this manual.
Verify proper circulator and speed for boiler size and system
requirements.
See message displayed TEMPERATURE SENSOR and follow procedure for
loose connections.
RETURN >
SUPPLY
Occurs if a return water
temperature is greater than
the corresponding supply
temperature by 10ºF or more.
Automatically resets when
condition no longer exists.
Verify proper flow direction of the boiler circulator. This circulator must
be installed to push water through the boiler's return pipe as shown on
page 38.
Verify proper boiler circulator speed setting in the WM97+ control.
Figure 110
Troubleshooting suggestions for WM97+ boilers —
Fault displays, diagnostics and corrective actions