How to read the last 3 lockout histories:
1. Scroll down to “DIAGNOSTICS” and press the
enter key (Square Key in center)
2. Scroll down to “ERRORS” and press the enter key
(Square Key in center)
3. Scroll down to “LOCKOUT HISTORY #” and press
the enter key.
4. Scroll to choose the either “MANUAL RESET” or
“AUTO RESET” and press the enter key to display
the fault condition that was recorded.
5. Press the left arrow key to return to the LOCKOUT
HISTORY # screen. Scroll up or down to highlight
other choices and press the enter key to view the
details of the boiler’s condition when the lockout
was recorded.
6. TO CLEAR ALL LOCKOUT HISTORIES: While on the
“ERRORS” screen, hold the Left and Right arrow
buttons simultaneously for 5 seconds.
Control Error Condition Log
The Control is able to record information about the boiler’s condition at the time of the three previous faults or errors. This infor-
mation is available to view in Contractor Menus under “DIAGNOSTICS” by selecting “PAST ERRORS.” The control will display
the following information:
Information
Description
Action
Control Fault
Records number
Select and press the enter key to reset this count
Ignition Retries
Displays the number of ignition attempts in the current
ignition sequence.
Manual Reset Count
Records number of lockouts that required a manual reset
since this count was last cleared.
Select and press the enter key to reset this count
Auto Reset Count
Records number of lockouts that have automatically reset
since this count was last cleared.
Select and press the enter key to reset this count
Lockout History 1
Details of present or last recorded lockout
Select and press the enter key for more details
Lockout History 2
Details of boiler during the second oldest lockout still in
memory
Select and press the enter key for more details
Lockout History 3
Details of boiler during the oldest lockout still in memory
Select and press the enter key for more details
Troubleshooting
(continued)
&IGURE
Troubleshooting suggestions for SlimFit boilers
RESET TO FACTORY DEFAULT
1. Selecting this will prompt the user to hold the enter button
for a specified length of time. Upon completion, this will
reset the control settings back to factory installed settings.
ONCE THIS IS CHOSEN, PREVIOUS SETTINGS CAN-
NOT BE RECOVERED. ENSURE THIS ACTION IS
TRULY DESIRED BEFORE CONTINUING.
2. Reset to Factory Default can be found on the BOILER
SETTINGS menu, see Figure 62, page 73.
How to clear all lockout histories:
1.
While on the “PAST ERRORS” screen, hold the
Left and Right arrow buttons simultaneously
for 7 seconds.