Part number 550-100-168/0516
98
&IGURE
Control display toggles when in lockout, with screen flashing red to gray
SlimFit
®
Series 3
COMMERCIAL
CONDENSING
GAS
-
FIRED
WATER
BOILER
—
Boiler Manual
Control fault indications
1. The Control provides diagnostic information for
both automatic reset conditions and manual reset
conditions. See Figure 58, page 70 for information
available on the Control display.
2. Figure 84 shows the screen behavior during an
automatic or manual reset condition. The table
below the display illustration lists manual reset conditions and how
to reset from them.
3. Figure 85, page 99 lists conditions that will cause the control to display
a constant red screen. The boiler will automatically restart if the con-
dition self-corrects or the technician uses the Control’s manual reset
screens to reset.
Make sure to determine the causes of outages. Do not leave the boiler operating without a complete diagnosis.