Part number 550-100-168/0516
123
&IGURE
Engineering data (see Figure 106 for notes)
SlimFit
®
Series 3
COMMERCIAL
CONDENSING
GAS
-
FIRED
WATER
BOILER
—
Boiler Manual
Ratings — multiple SlimFit Series 3 boilers
(continued)
1
Foundation sizes in Figure 104 provide 12 inches between boilers and approximately 2 inches from boiler to edge of foundation.
Smaller foundations are possible with reduced service clearances.
See page 7 for details.
s
For side-to-side installations, see Advanced Control Manual.
s
For back-to-back installations, see Advanced Control Manual.
2
Operating weight is the total weight of the boiler, including water.
3
All SlimFit installations require a separate vent pipe and termination for each boiler.
6ENTPIPINGCANNOTBEMANIFOLDED
. Install and
terminate vents as described in vent/air installation instructions in this manual.
Combustion air piping can be individually piped or manifolded. See Figure 26, page 36, for manifolded air piping.
4
Boiler total amp load is 18 amps, which includes up to three circulators not exceeding 2.2 amps per circulator. Electrical service
required is the minimum recommended breaker or fuse size. DO NOT use larger than a 30-amp breaker or fuse.
In addition, circulator #4 requires a separate power supply for circulator amperage not to exceed 10 amps. Electrical service required
is the recommended breaker size of 15 amps. DO NOT use a higher-amp-rated breaker or fuse.
Boiler
Model
Shipping
weight
Operating
weight
Water
content
Water flow rate
per boiler
Vent/air pipe
size —
Provide a
separate vent
for each boiler
Electrical
service
required
Pounds
per boiler
Pounds
per boiler
Gallons
per boiler
GPM
@ 30°F rise
GPM
@ 40°F rise
Amps
per boiler
Note 2
Note 3
Note 4
SF-550
505
476
5.5
34
26
6” or 8”
25 (boiler)
15 (Boiler
Circulator)
SF-750
550
529
6.5
47
35
6” or 8”
25 (boiler)
15 (Boiler
Circulator)
&IGURE
Notes for Figure 104 and Figure 105
Installation and Service Certificate
"OILER$ATA
"OILER-ODEL3ERIES
SlimFit
????????3ERIES????
$ATEINSTALLED?????????????????????
#0.UMBER????????????????
&5%,.ATURAL??????,0??????
"TU)NPUT???????????????????
#%24)&)%$4(!4
:
❏
Installation instructions have been followed.
❏
Check-out sequence has been performed.
❏
Information on next two pages is certified to be correct.
❏
Information received and left with owner/maintenance person.
Installer
(Company) (Address) (Phone) (Installer’s Signature)