![Weil-McLain 550 MBH Скачать руководство пользователя страница 102](http://html1.mh-extra.com/html/weil-mclain/550-mbh/550-mbh_nstallation-and-operation-manual_952622102.webp)
Part number 550-100-168/0516
102
SlimFit
®
Series 3
COMMERCIAL
CONDENSING
GAS
-
FIRED
WATER
BOILER
—
Boiler Manual
&IGURE
Troubleshooting suggestions for SlimFit boilers
(continued)
Display
Condition
Diagnostics
Corrective Action(s)
LIMIT OPEN
Occurs if manual or automatic
reset l imit op ens.
Automatic external limit will
reset 2½ minutes after external
limit device closes.
Manual limit fault must be reset
by choosing Manual Reset on
the display.
Is there an external safety device connected? If yes, trouble shoot the
external limit to determine and correct the cause that opened the limit.
Also check for loose wiring connections.
Remove the top right Control tray cover and inspect the connector.
Ensure a jumper is installed across the MAN LIMIT terminals if not using a
manual reset external limit.
Ensure a jumper is installed across the AUTO LIMIT terminals if not using
a automatic reset external limit.
HIGH TEMP
LIMIT
Boiler temperature sensor
reached High Temp Limit
setting (no higher than 200° F).
Reset using manual reset screen
on display.
Verify that high limit setting is at least 10° F above the
maximum
target
temperature
plus the off differential
.
Verify all isolation valves are open and circulators are programmed into
the control properly.
The boiler circulator output and System Pump/Aux. output can be
configured to turn on or off with each priority. Refer to the Control Setup
section to configure these properly for the system.
Verify water pipe is installed correctly per instructions in this manual.
Verify proper circulator sizing for boiler size and system requirements.
See message displayed TEMPERATURE SENSOR and follow procedure for
loose connections.
FLAME FAULT
Occurs if flame is detected
when there should be no
flame.
Reset using manual reset screen
on display.
Burner may be operating too hot due to incorrect combustion. Inspect
flame and conduct combustion test.
Force boiler into high fire. Check flue gases with combustion analyzer
and correct using the maintenance and startup procedure in this manual.
Verify FLAME SIGNAL value quickly goes to zero on the DIAGNOSTICS -
INPUTS screen when the gas valve closes.
Check for flame at burner via flame current with burner off. Turn boiler
off and watch flame through observation port. If flame continues after
shut down replace gas valve.
BLOWER FAULT
Blower unable to reach
required speed or does not
reach 0 RPM when turned off.
Reset using manual reset screen
on display; Control will check
again after 1 hour and will
automatically restart if condition
is corrected.
Check wire harness for loose connections and pin engagement at
blower connections, chassis mount connection through control housing,
and control. Unplug connection at blower and at control and check
continuity between ends. Blower is connected to both low voltage and
line voltage harness.
Check Diagnostics - Inputs screen with boiler in standby mode and
blower not running. If BLOWER SPEED is not 0 RPM then replace blower.
If blower does not rotate during ignition sequence check for 120V power
at blower connection. If 120 VAC power at blower motor and it doesn't
start replace blower. Check power at control. If 120VAC is not present
at control when boiler is powered replace Control. Refer to repair parts
section.
Troubleshooting
(continued)