4 Module descriptions
| Digital input and output modules IP67, PROFIBUS, 60 mm, metal housing
25
2484950000/00/03.2016
Manual UR67-PROIFBUS
Bit 7
6
5
4
3
2
1
0
Channel related diagnosis
Byte 10
1
0
0
0
0
0
0
0
Byte 11
Input: 01
Output: 10
Channel number: 0 ... 15
Channel no. 0 = socket 1, channel A
Channel no. 1 = socket 1, channel B
usw.
Channel no 15 = socket 8, channel B
Byte 12
Channel type: Bit: 001
Error type:
Only error type 1 is used.
Indicating a diagnosis in STEP 7
▶
Choose the affected I/O module in the hardware manager
by a mouseclick.
▶
Open the menue "Target system – Component state –
DP Slave Diagnosis“
To display the diagnosis in hexadecimal format and display
its structure, click the button „Hex View“.