Set up and Programming
2. Selecting and Setting Outlet Water Temperature Set-point:
Touch the icon which will direct you to the System Menu which will appear as:
WARNING
!
BEFORE setting mixed outlet water
temperature or electing default tempera-
ture, point-of-use mixing valves and/or
temperature limiting devices MUST be
installed at all fixtures (faucets, sinks,
tubs, showers, etc.)
BAS Setpoint Max
140 °F
Mixed Out Setpoint
140 °F
Pump Operation
Auto
Pump Min On/Off Time
1 min
High Temp Alert
150 °F
Pump Head
0.0 psi
Return Target
130 °F
Return Differential
Back
Up
Down
System
Enter
?
10 °F
OMM-0126-0A