Flow Capacity at 50-50 mixed ratio
P r e s s u r e D r o p A c r o s s V a l v e
Model
Min.
System
Draw*
C
V
5psi
(34 kPa)
10psi
(69 kPa)
20psi
(138 kPa)
30psi
(207 kPa)
45psi
(310 kPa)
50psi
(345 kPa)
ADMS150
0.50
26.88
60 gpm
227 lpm
85 gpm
322 lpm
120 gpm
454 lpm
147 gpm
556 lpm
180gpm
681 lpm
190 gpm
719 lpm
ADMS200
0.50
42.70
96 gpm
363 lpm
135 gpm
511 lpm
191 gpm
723 lpm
234 gpm
886 lpm
286 gpm
1083 lpm
302 gpm
1143 lpm
ADMS150D
0.50
53.57
120 gpm
454 lpm
170 gpm
644 lpm
240 gpm
908 lpm
294 gpm
1113 lpm
360 gpm
1363 lpm
380 gpm
1439 lpm
ADMS200D
0.50
85.27
192 gpm
727 lpm
270 gpm
1022 lpm
382 gpm
1446 lpm
468 gpm
1772 lpm
572 gpm
2165 lpm
604 gpm
2286 lpm
ADMS200T
0.50
127.90 288 gpm
1090 lmp
405 gpm
1533 lpm
573 gpm
2169 lpm
702 gpm
2657 lpm
858 gpm
3248 lpm
906 gpm
3430 lpm
ADMS Description and Specifications
Specifications
Maximum Operating Pressure ...................................................... 200psi (1379 kPa)
Maximum Hot Water Temperature ........................................................ 200°F (93°C)
Minimum Hot Water Supply Temp.** ........................... 2°F (1°C) Above Set Point
Hot Water Inlet Temperature Range .................................... 120 – 180°F (49-82°C)
Cold Water Inlet Temperature Range ......................................... 39 – 80°F (4-27°C)
Minimum Flow*** ........................................................................... 0.5 gpm (1.89 lpm)
Outlet Water Temperature Adjustment Range**** ............. 80 – 180°F (27-82°C)
Listing/Compliance .............................. ASSE1017
®
, cUPC
®
, NSF
®
, CSA 24/UL873
* The wetted surface of this product contacted by consumable water contains less than 0.25% of lead by weight.
** With Equal Pressure
*** Minimum flow when ADMS is installed at or near hot water source recirculating tempered water with a
properly sized continuously operating recirculating pump.
**** Low limit cannot be less than the cold water temperature. For best operation, hot water should be at
least 5°F (3°C) above desired set point.
Technical Specifications
Input Power ....................................115 V ±10%, 60 Hz, 30 VA, 1180 VA fully loaded
Pump relay ............................................ 115/230 V: 10/8 FLA, 50/48 LRA Motor Load
Alert relay: ...................................................30 V (ac/dc) max. 2 A, resistive, Class 2
5 V capacity: ..............................................10 mA maximum each, resistive, Class 2
20 V capacity:............................................20 mA maximum each, resistive, Class 2
Actuator load: ...........................................................................................................20 VA
Meets Class B: ...........................................................................ICES and FCC Part 15
Capacity
*With a properly sized pump
^ Listed without re-circulation line & pump
!
User is responsible for determining safe and appropriate
temperatures and pressures for system users, guests and facility.