Scheduled Testing, Inspection and Maintenance
Maintenance
■
Actuator and/or Valve Removal
■
Actuator Removal Instructions
Valves and actuators are not field serviceable. They must be removed and replaced.
NOTICE
BEFORE attempting to open Control
Module, a certified and qualified elec-
trician MUST fully de-energize and
disconnect all electrical power from
ADMS.
Perform required LOCK OUT/TAG OUT
procedures.
When done, reconnection and reener-
gizing of ADMS
MUST
be performed by
certified and qualified electrician.
DANGER
!
Tools Required:
• 10mm and
3
/
8
" sockets, elbow and torque wrench. Not required if replacing both valve and actuator
•
3
/
8
" wrench. Not required if replacing both valve and actuator
• 2.5mm Allen key. Not required if replacing both valve and actuator
•
1
/
8
" (3.2mm, #2) slot screwdriver. Not required for valve only replacement
• Wire Stripper and snips. Not required for valve only replacement
• AC Voltmeter . Not required for valve only replacement
• Five to ten 4" zap straps (cable ties)
• 4" monkey wrenches (gas grips)
• 3" adjustable wrenches (shifting spanner)
• Teflon Tape. Not required for actuator only replacement
OMM-0126-0A
Page 64 of 71