AERCO ADMS BAS Integration Manual
Vendor Name: tekmar Control Systems Ltd.
Vendor ID: 983
Product Name: ADMS Smart Water Tempering System
Product Model Number: 106902
Application Software Version: J1268A
BACnet Protocol Revision: 10
Product Description:
The ADMS is a mixing control designed to deliver tempered water to plumbing fixtures. The control
uses a Proportional Integral (PI) logic to accurately maintain a target temperature by mixing a high
temperature water source with a low temperature water source. This control also offers advanced
features including communication with a Building Automation System (BAS).
BACnet
®
Protocol Implementation Statement (PICS)
!
ADMS provides user-directed control and monitoring of water distribution
systems. It is the user’s responsibility to select and maintain water
temperatures and pressures that are safe and appropriate for the water
system users, guests and facility. ADMS’ Sanitization mode is intended
for use as part of a user-directed, controlled and supervised protocol
that has been safely and properly designed. It is recommended to install
ADMS
™
as part of a ASSE 1070 compliant water distribution system,
including point-of-use mixing valves. Always read and follow User
Guide & Instruction Manual and all product warnings and labels, and
comply with all governmental and safety requirements.
BACnet Standardized Device Profile (ANNEX L)
BACnet Application Specific Controller (B-ASC)
Supported BIBBs (Annex K)
Name
DS-RP-B
Data Sharing-ReadProperty-B
DS-RPM-B
Data Sharing-ReadPropertyMultiple-B
DS-WP-B
Data Sharing-WriteProperty-B
DM-DDB-B
Device Management-Dynamic Device Binding-B
DM-DOB-B
Device Management-Dynamic Object Binding-B
DM-DCC-B
Device Management-Device Communication Control-B
Note: Device communication control password is “AERCO1017”.
Segmentation Capability
Supported
Able to transmit segmented messages
No
Able to receive segmented messages
No
Standard Object Types Supported
Creatable
Deletable
Analog Input
No
No
Analog Value
No
No
Binary Output
No
No
Data Link Layer
Supported
BACnet
®
IP (Annex J)
Yes
BACnet
®
MSTP
Yes
Device Address Binding
Supported
Static Device Address Binding
No
Network Security Options
Non-Secure Device
Character Set
Supported
ANSI X3.4
Yes
OMM-0126-0A