Troubleshooting
Problem:
Solution:
Unstable control is observed at flow rates greater than the minimum
rated flow
Balancing Routine
WARNING
!
To avoid scalding, burning, thermal shock or
other hazards DO NOT use or allow anyone to
use the water at any point-of-use fixture (faucets,
sinks, tubs, showers, etc.) in the facility's water
distribution system during Balancing Routine.
The Balancing Routine can cause higher tem-
perature water in the system and delivered to
point-of-use fixtures (faucets, sinks, showers,
etc.). Only qualified and authorized personnel
who fully understand the Balancing Routine's
operation, output and risks, should perform this
action.
Personnel performing Balancing Routine and the
owner or manager of the water distribution sys-
tem MUST take appropriate safeguards to pro-
tect people from using, contacting or exposure
to water or any parts of the water distribution
system. Always read and follow the User Guide
& Instruction Manual.
1. The Balancing Routine is designed to give the software additional information regarding the normal
operating balance of the system to eliminate the need for a balancing valve.
2. To conduct the Balancing Routine it is necessary to generate a load larger than the minimum rated
flow rate using the following procedure.
3. Attach a 1" hose to the pump inlet hose connection and ensure that the other end of the hose is
securely routed to a drain.