Sanitization
The Sanitization function produces high tempera-
ture water at all point-of-use fixtures (faucets,
sinks, tubs, showers, etc.). Only qualified and
authorized personnel who fully understand the
function's operation, output and risks, should use
the Sanitization function, and only as part of and
in compliance with, a thermal eradication protocol
safely and properly designed by the owner or man-
ager of the water distribution system. The owner
or manager of the water distribution system has
sole responsibility to protect end-users, facility
employees or contractors, personnel performing
the Sanitization, and bystanders from scalding,
burning, thermal shock, or other hazards from pos-
sible exposure to water or any parts of the water
distribution system during Sanitization and cool
down period, until system water returns to a safe
and proper outlet water temperature set point.
Always read and follow the User Guide & Instruction
Manual.
DANGER
!
The Sanitization function produces high water temperatures and is intended
ONLY
for use as part
of a user-directed, controlled and supervised thermal eradication protocol that has been safely and
properly designed to help limit water-borne bacteria within the tempered water distribution system.
The instructions contained in this Manual for the Sanitization function are not intended to be a thermal
eradication protocol.
Selecting, directing, and controlling a safe and properly designed thermal eradication protocol is the
sole responsibility of the people who own, manage or control the water distribution system. It is their
responsibility to protect water distribution end-users, facility employees or contractors, and bystanders
from scalding, burning, thermal shock, or other hazards from possible exposure to water or any parts of
the water distribution system during Sanitization and cool down period, until system water returns to a
safe and proper outlet water temperature set point.